– 48 –
5
Chapter
ON/OFF Control Hysteresis
to
The following sets the hysteresis during ON/OFF control.
Up to seven types of hysteresis (palettes 1 to 7) can be
recorded. Recorded hysteresis can be recalled from
selected PID number ("
PPP
PLLLLnnnn1111
") in the operation menu.
• Range: 0% to 50% FS
Setting ON/OFF Control Hysteresis
The following steps explain how to set ON/OFF hysteresis
control using 3.0°C as an example.
Refer to
See "ON/OFF Hysteresis Control" (p. 32) for more information
about ON/OFF control hysteresis.
Point
When PID parameter P = 0, ON/OFF control is used.
1
Press and hold the
key to display the setup
mode channel menu ("
ooo
oPPPPEEEE CCCChhhh 1111
") then use the
keys to display PLT ("
PPP
PLLLLTTTT CCCChhhh 3333
").
Refer to
See p. 46 in this chapter for information on how to display
the channel menu.
2
Press and hold the
key to display the SV
parameter ("
SSS
Svvvv 1111
"), then use the
keys to
display hYS1 ("
hhh
hYYYYSSSS1111
").
3
Press the
key, then use the
keys to
set ON/OFF control hysteresis to 3.0 when the
bottom part of the display begins to blink.
The hysteresis is set to 3.0°C.
4
Press the
key to confirm the setting.
5
Press the
key to return to the operation mode
PV/SV display.
Cooling Proportional Band
to
Sets the cooling proportional band when dual outputs
are selected. Up to seven types of cooling proportional
band (palettes 1 to 7) can be recorded. Recorded cooling
proportional band can be recalled from selected PID
number (“
PPP
PLLLLnnnn1111
”) in the operation menu.
• Range: 0.0 to 100.0
Setting Cooling Proportional Band
The following steps explain how to set cooling proportional
band using 5.0% as an example.
Refer to
See "Cooling Proportional Band Coefficient" (p. 33) for more information
about cooling proportional band.
1
Press and hold the
key to display the setup
mode channel menu ("
ooo
oPPPPEEEE CCCChhhh 1111
") then use the
keys to display PLT ("
PPP
PLLLLTTTT CCCChhhh 3333
").
Refer to
See p. 46 in this chapter for information on how to display
the channel menu.
2
Press and hold the
key to display the SV
parameter ("
SSS
Svvvv 1111
"), then use the
keys to
display CoL1 ("
CCC
CooooLLLL1111
").
3
Press
, then use the
keys to set the
cooling proportional band to "5.0".
The cooling proportional band is set to 5.0.
4
Press the
key to confirm the setting.
5
Press the
key to return to the operation mode
PV/SV display.
Summary of Contents for PXG4
Page 1: ...c...
Page 10: ...9 1 Chapter Chapter 1 Part Names and Functions Part Names and Functions 10...
Page 21: ...20 MEMO 2 Chapter...
Page 43: ...42 MEMO 4 Chapter...
Page 53: ...52 MEMO 5 Chapter...
Page 71: ...70 MEMO 7 Chapter...
Page 89: ...88 MEMO 8 Chapter...
Page 106: ...105 9 Chapter Behavior when control is lost Limit Cycle PV SV Time tuning MV control lost 100...
Page 119: ...118 MEMO 10 Chapter...
Page 125: ...124 MEMO 11 Chapter...
Page 131: ...130 MEMO 12 Chapter...
Page 141: ...140 MEMO 14 Chapter...
Page 151: ...150 MEMO 15 Chapter...
Page 152: ...151 16 Chapter Chapter 16 Troubleshooting Troubleshooting 152...
Page 157: ...156 MEMO 17 Chapter...