OUT1 Proportional Cycles
,
OUT2 Proportional Cycles
When using contact output and SSR drive output with PV
input inside the proportional band, output will switch ON/
OFF at regular intervals.
These intervals are called proportional cycles. OUT1 and
OUT2 can be set separately.
• Range: 1 sec to 150 sec
There are different recommended settings for different types
of control output, as shown below.
Setting the Preset OUT1/OUT2 Values
Contact Output
The shorter the proportional cycle, the
finer the control, however shorter
proportional cycles also shorten the
lifespan of the contact points and
operating device. Be sure to balance
control and controller lifespan when
adjusting the proportional cycles.
Approx.: 30 sec
SSR Drive Output
Because there are no mechanical parts to
this controller, use a short proportional cycle
if the operating device is working properly.
Approx: 1 sec to 2 sec
Caution
• TC2 is only valid when there are dual outputs.
• It cannot be set for current output or voltage output.
output ON
proportional
cycle
proportional
cycle
1
Press and hold the
key to display the setup
mode channel menu ("
ooo
oPPPPEEEE CCCChhhh 1111
"), then use the
keys to display Pid ("
PPP
Piiiidddd CCCChhhh 2222
").
Refer to
See p. 31 in this chapter for information on how to display
the channel menu.
2
Press and hold the
key to display P ("
PPP
P
"), then
use the
keys to display TC1 ("
TTT
TCCCC1111
").
Specify the proportional cycle for OUT1.
3
Press the
key, then use the
keys to set
the limit to 60.
The proportional cycle for OUT1 is set to 60 seconds.
4
Press the
key to confirm the setting.
5
Repeat steps 2-4 (excluding pressing and holding
the
key) to set the proportional cycle for
OUT2.
6
Press the
key to return to the operation mode
PV/SV display.
Summary of Contents for PXG4
Page 1: ...c...
Page 10: ...9 1 Chapter Chapter 1 Part Names and Functions Part Names and Functions 10...
Page 21: ...20 MEMO 2 Chapter...
Page 43: ...42 MEMO 4 Chapter...
Page 53: ...52 MEMO 5 Chapter...
Page 71: ...70 MEMO 7 Chapter...
Page 89: ...88 MEMO 8 Chapter...
Page 106: ...105 9 Chapter Behavior when control is lost Limit Cycle PV SV Time tuning MV control lost 100...
Page 119: ...118 MEMO 10 Chapter...
Page 125: ...124 MEMO 11 Chapter...
Page 131: ...130 MEMO 12 Chapter...
Page 141: ...140 MEMO 14 Chapter...
Page 151: ...150 MEMO 15 Chapter...
Page 152: ...151 16 Chapter Chapter 16 Troubleshooting Troubleshooting 152...
Page 157: ...156 MEMO 17 Chapter...