Output Convergence Value
Output convergence value is a function that adds MV
value offset.
• Range bAL : -100% to 100%
●
The output convergence value function ("
bbb
bAAAALLLL
") outputs to
PV and SV a calculated result of the PID computed MV
plus the bAL offset.
(The factory setting of bAL is 0% for single output, 50% for
dual output.)
Setting the Output Convergence Value
proportional
band
MV
bAL=40%
50%
PV
SV
40%
bAL=0%
100%
1
Press and hold the
key to display the setup
mode channel menu ("
ooo
oPPPPEEEE CCCChhhh 1111
"), then use the
keys to display Pid ("
PPP
Piiiidddd CCCChhhh 2222
").
Refer to
See p. 31 in this chapter for information on how to display
the channel menu.
2
Press and hold the
key to display P ("
PPP
P
") then
use the
keys to display bAL ("
bbb
bAAAALLLL
").
Set the output convergence value.
3
Press the
key, then use the
keys to set
the output convergence value to "3.0".
The output convergence value is set to 3.0.
4
Press the
key to confirm the setting.
5
Press the
key to return to the operation mode
PV/SV display.
Summary of Contents for PXG4
Page 1: ...c...
Page 10: ...9 1 Chapter Chapter 1 Part Names and Functions Part Names and Functions 10...
Page 21: ...20 MEMO 2 Chapter...
Page 43: ...42 MEMO 4 Chapter...
Page 53: ...52 MEMO 5 Chapter...
Page 71: ...70 MEMO 7 Chapter...
Page 89: ...88 MEMO 8 Chapter...
Page 106: ...105 9 Chapter Behavior when control is lost Limit Cycle PV SV Time tuning MV control lost 100...
Page 119: ...118 MEMO 10 Chapter...
Page 125: ...124 MEMO 11 Chapter...
Page 131: ...130 MEMO 12 Chapter...
Page 141: ...140 MEMO 14 Chapter...
Page 151: ...150 MEMO 15 Chapter...
Page 152: ...151 16 Chapter Chapter 16 Troubleshooting Troubleshooting 152...
Page 157: ...156 MEMO 17 Chapter...