-30-
4.7. Switching measurement mode
4.7.1. Setting measurement mode and CH3 (calculation output)
Description
Measurement mode can be selected.
When 2-pipe measurement is selected, the calculation formula for CH3 can be configured.
Settable range
1. Measurement mode : 1-path, 2-path, 2-pipe
・
1 PATH : Measure flow rate and thermal energy in 1 pipe using 1 set of detector
・
2 PATHS : Measure flow rate in 1 pipe using 2 sets of detector
・
2 PIPES : Measure flow rates in 2 separate pipes using 1 set of detector for each pipe.
2. CH3 calculation output : average, addition, subtraction (CH1-CH2), subtraction (CH2-CH1)
When selecting 2-pipe measurement mode:
・
AVERAGE
=
(path 1 + path 2
)
/ 2
・
ADDITION
=
path 1 + path 2
・
SUB (CH1-CH2)
=
path 1 - path 2
・
SUB (CH2-CH1)
=
path 2 - path 1
* When selecting 2-path measurement mode, average value is output for CH3.
* When selecting 1-path or 2-path measurement mode, there is no setting items of CH3.
For actual keying, refer to the typical operation indicated below. Set the protection to OFF beforehand. (See Section 4.5.1.)
Operation
(example)
Set measurement mode to 2-pipe and CH3 calculation output to subtraction (CH1-CH2).
Key operation
Description
Display
0.000 m/s
0.000 m3/h
▼
Press the
key 3 times to display “MEASURE SETUP”.
MEASURE SETUP
ENT
▼
Press the
ENT
key once to display “MEASUREMENT MODE”.
MEASUREMENT MODE
1 PATH
ENT
▼
Press the
ENT
key once to blink the second line.
MEASUREMENT MODE
1 PATH
▼
Press the
key twice to display “2 PIPES”.
MEASUREMENT MODE
2 PIPES
Press the
ENT
key once to save the change.
MEASUREMENT MODE
COMPLETE
↓
ENT
▼
▼
▼
▼
―――
2 PIPES has been registered.
―――
“CH3 CALCULATION” is displayed.
CH3 CALCULATION
AVERAGE
ENT
▼
Press the
ENT
key once to blink the second line.
CH3 CALCULATION
AVERAGE
▼
Press the
key twice to display “SUB (CH1-CH2).
CH3 CALCULATION
SUB (CH1-CH2)
Press the
ENT
key once to save the change.
CH3 CALCULATION
COMPLETE
↓
ENT
▼
▼
▼
▼
―――
SUB (CH1-CH2) has been registered.
――
“CH3 CALCULATION” is displayed.
CH3 CALCULATION
SUB (CH1-CH2)
ESC
Press the
ESC
key twice, and then the
key twice to return to the
measurement mode.
0.000 m/s
0.000 m3/h