2. Main Menu Screen
9-1.
Self-loop Test
This is a signal test for communications through the COM1, COM2 or COM3 connector.
Perform this test if the communication is not successfully established when connecting a controller
(PLC, temperature controller, etc.) using COM1, COM2 or COM3.
COM1: RS-485 Signal Test
SD/RD Test
Check the signals [SD] and [RD].
1. Set DIP switch Nos. 2 and 3 to OFF.
* Turn the power off when setting DIP switches.
2. Install a jumper between pins 1 and 4, and between pins 2 and 3 of COM1 on the TS series.
3. Press the [COM1] switch in the [Communication Port] field. The [RS485] lamp comes on.
4. Press the [Self-Loop Test] switch. When the [OK] lamp lights up, the test is successfully
completed.
* If the [NG] lamp lights up, a pin may be faulty. Contact your local distributor.
COM1 (D-sub 9-pin, female)
COM2 / COM3 (D-sub 9-pin, male)
9
5
6
1
6
1
9
5
-RD
+RD
1
2
Name
No.
+SD
-SD
3
4
Summary of Contents for MONITOUCH TS Series
Page 1: ......
Page 10: ...11 Features 2 Models and Peripheral Equipment 3 System Composition Product Outline ...
Page 43: ...2 26 6 LAN Connector TS1100i TS1070i Only Please use this page freely ...
Page 44: ...31 Mounting Procedure 2 Power Supply Cable Connection Installation ...
Page 49: ...41 Coin type Lithium Battery 2 DIP Switches Handling of TS Series Components ...
Page 57: ...4 8 2 DIP Switches Please use this page freely ...
Page 58: ...51 Before Operation 2 Main Menu Screen 3 System Menu TS Series Operations ...
Page 102: ...5 44 3 System Menu Please use this page freely ...
Page 103: ...61 Error Messages 2 Troubleshooting Error Handling ...
Page 110: ...71 Inspection and Maintenance 2 Warranty Policy Inspection and Maintenance ...
Page 114: ...7 4 2 Warranty Policy Please use this page freely ...