USER’S MANUAL

Conformance with Standards

FEH249

SERIES

Summary of Contents for MICREX-SX Series SPH

Page 1: ...USER S MANUAL Conformance with Standards FEH249 SERIES ...

Page 2: ...ucts that conform to various standards CE marking Lloyd s Register of Shipping etc Please read this manual carefully to correctly use your device If your MICREX SX Series product does not need to conform to CE marking or Lloyd s Register of Shipping there is no need to execute the content of this manual There will be no problem with performance and functionality If your MICREX SX Series product is...

Page 3: ... Manual No is shown on the cover Revision Printed on Manual No Revision contents May 2000 FEH249 First edition ...

Page 4: ... link master interface module NP1L TL1 RT1 2 4 2 OPCN 1 master module NP1L JP1 2 5 3 FL net OPCN 2 module NP1L FL1 2 5 4 Precautions for using the AS i master module NP1L AS1 2 6 5 DeviceNet master module NP1L DN1 2 6 6 Measures for the positioning modules 2 7 Seciton3 Adaptation to UL standard Lloyd s Resister of Shipping NK 3 1 Adaptation to UL standard 3 1 3 2 Adaptation to Lloyd s Resister of ...

Page 5: ...ken NP1C P6 Cable length 60cm yes yes yes yes yes NP1C P8 Cable length 80cm yes yes yes yes yes NP1C 02 Cable length 2m yes yes yes yes yes NP1C 05 Cable length 5m yes yes yes yes yes NP1C 10 Cable length 10m yes yes yes yes yes NP1C 25 Cable length 25m yes yes yes yes yes SX bus T branch uint NP8B TB For SX bus T branch yes yes yes yes yes Digital input module NP1X1606 W 24V DC 16 points yes yes ...

Page 6: ...its yes yes yes yes yes NP1AX04 MR 4 channels Resolution 10bits yes yes yes yes yes NP1AX08 MR 8 channels Resolution 10bits yes yes yes no no Multi range Analog output module NP1AYH2 MR 2 channels Resolution 10bits yes yes yes yes yes NP1AY02 MR 2 channels Resolution 10bits yes yes yes yes yes General purpose communication module NP1L RS1 RS 232C 1 channel RS 485 1 channel yes yes yes yes yes NP1L...

Page 7: ... D300win cable NP4H CNV Personal computer cable for loader with converter yes yes yes yes yes NP4H CA2 Personal computer cable for loader yes yes yes yes yes Simulative input swich NP8X SW 16 points yes yes yes yes yes Data backup battery NP8P BT Lithium primary battery yes yes yes yes yes User ROM card NP8PMF 16 User ROM card 16k steps Dedicated to standard CPU yes yes yes yes yes CPU mode select...

Page 8: ...voltage Category II EMC classification when installing PLC defined in IEC 61131 2 Zone B which is defined as follows An environment where power from an external power supply which supplies power to the factory the build ing in which the device is installed is used after doubly protecting against surge voltage with an insulating transformer or the like 3 phase power supply Primary protection Second...

Page 9: ...Series products also need to be installed in a metal enclosure in order to control the electro magnetic radiation noise EMI they emit Basic specifications for the metal enclosure are as follows Material SPCC high tensile strength steel Plate thickness Min 1 6 mm Power supply Power supplied to the control panel should be protected from external surge voltage with an insulating transformer Remarks S...

Page 10: ...o affix the cable to the metal enclosure When affixing the SX bus cable to the metal enclosure be sure to secure a 1 cm or wider gap so that the SX bus cable does not come into contact with the metal plate On the one hand the metal enclosure provides an effective shield fromelectromagnetic radiation noise on the other hand it becomes an effective antenna that electromagnetic radiation noise if a c...

Page 11: ... of a static elimination band or the like before touching the station number set ting switch This is necessary only for the T link master module NP1L TL1 and not necessary for the T link interface module NP1L RT1 Ferrite core mounting may be unnecessary if all of the communication cable is laid only inside the metal enclosure or even when it is laid outside the metal enclosure if it is laid in EMI...

Page 12: ...unication cable a ferrite core needs to be mounted at the base of the cable 1 Mount the ferrite core at the base of the communication cable Affix the insulating sheet supplied with the product on the station number setting switch Note For the purpose of explanation a colored sheet is used in the photo at left The actual insulating sheet supplied with the product is transparent Commendable ferrite ...

Page 13: ...AT 3035 1330 from TDK Note If vibration or shock is applied to the product a strong force due to the weight of the ferrite core may act on the cable to damage it Be sure to af fix the cable to a firm object such as a duct so that the cable does not swing under vibration Ferrite core mounting may be unnecessary if all of the communication cable is laid only inside the metal enclosure or even when i...

Page 14: ... does not occur Commendable ferrite core ZCAT 3035 1330 from TDK Note If vibration or shock is applied to the product a strong force due to the weight of the ferrite core may act on the cable to damage it Be sure to af fix the cable to a firm object such as a duct so that the cable does not swing under vibration 2 Affix the static electricity preventive insulating sheet on the station number setti...

Page 15: ...vere in the former than in the latter Therefore when a MICREX SX Series product is used for marine equipment tightly wind a strong nylon band around the entire PLC so that the modules come in close contact with each other as shown in the figure below A guideline for checking the propriety of the contact is whether or not a name card can be inserted in between the mod ules Fix by tightly winding a ...

Page 16: ... the PC unit as far from high voltage device high voltage cables or power equipment as possible Avoid installing PC I O cables unit and high voltage or power equipment cables in parallel 5 Install the PC unit perpendicular to the panel floor 6 The PC must be installed in a vertical position Do not install the PC in other position Section4 Installing the PC Wiring of power supply 80mm or more Unite...

Page 17: ...6 4V DC The thickness of the wire must be 2mm2 and the wire must ne twisted densely Tips The tolerance range of MICREX SX AC power supply is 85 to 132V AC for 100V AC and 170 to 264V AC for 200V AC But the voltage is recommended to be as near the rated voltage 100 to 110V AC 200 to 220V AC as possible In the case of the lower voltage a small voltage drop will cause a power failure In the case of t...

Page 18: ...addition keep the distance at which they run in parallel as short as possible For grounding use an exclusive ground pole and wire which are separated from the ground system of other power cir cuits The grounding should be exclusive The grounding resistance is 100 or less Separate the ground pole 10m or more from that of other power circuit When installing in a place affected by frequent lighting s...

Page 19: ... FG FG T link master 2mm2 FG bus Operator panel Remote I O FG POD FG bus 5 5mm2 or more Integrated ground board Grounding Section4 Installing the PC Wiring of power supply Power supply Power supply Integrated ground section Integrated ground section ...

Page 20: ...trical Components Drive Systems Company Gate City Ohsaki East Tower 11 2 Osaki 1 chome Shinagawa ku Tokyo 141 0032 Japan Phone 3 5435 7135 3 5435 7136 Fax 3 5435 7456 3 5435 7457 Information in this manual is subject to change without notice ...