background image

1

FVR-C9S-7UX

Instruction Manual
FVR-C9S-7UX Drive Series

Single-phase 240 V AC Input Type

Summary of Contents for FVR-C9S-7UX

Page 1: ...1 FVR C9S 7UX Instruction Manual FVR C9S 7UX Drive Series Single phase 240 VAC Input Type...

Page 2: ...wiring operating and inspecting this drive Please make sure that this instruction manual accompanies the drive to the end user Keep this instruction manual so that it will always be available for the...

Page 3: ...ety Precautions 4 1 Inspection Upon Receipt 6 2 Part Names 7 3 Warning and Caution 7 4 Specifications 8 5 External Dimensions 10 6 Installation Instructions 12 7 Wiring 12 8 Basic Wiring Diagrams 14 9...

Page 4: ...its cover when trans porting Otherwise the drive could be damaged and cause injury to personnel Do not let any scraps of thread paper sawdust dirt metal shavings or other foreign objects get inside t...

Page 5: ...wer supply being connected matches the input phase and rated input voltage of the drive Using an improper power supply may cause injury or damage to the equipment Do not connect AC power to the output...

Page 6: ...VRF12C9S 7UX 0 98 14 FVRF25C9S 7UX 0 98 14 FVRF50C9S 7UX 0 98 14 FVR001C9S 7UX 0 98 14 FVR002C9S 7UX 0 98 14 Control board terminal 0 7 24 Use the listed quick acting fuse in series Fac tory recommend...

Page 7: ...ect the power supply to voltage that exceeds the standard speci fication voltage with permissible fluctua tion Permissible voltage AC220V 240V 2 Do not connect power supply to the drive output termina...

Page 8: ...variable in increments of 1 Hz Output Accuracy Analog setting 1 0 of max frequency 25 10 C frequency Digital setting 0 01 of max frequency 10 50 C Setting resolution Analog setting 1 255 of max freque...

Page 9: ...1 min 100 1 min 50 1 min Braking DC brake Brake starting frequency 3 Hz fixed Setting of braking current braking time is variable Overload Detects overload current and stops drive Momentary overcurren...

Page 10: ...08 27 5 0 59 15 DWG 1 FVRF50C9S 7UX 2 1 3 96 100 5 1 48 37 5 0 98 25 FVR001C9S 7UX 3 7 5 53 140 5 2 46 62 5 1 97 50 3 15 80 2 64 67 2 0 20X0 24 2 5 X 6 2 0 26 6 5 0 06 1 5 0 26 6 5 4 72 120 1 97 50 2...

Page 11: ...4 5 53 140 5 3 05 77 5 2 56 65 DWG 2 7 005 3 86 98 2 dia 0 20 2 dia 5 0 24 6 2 0 18 4 5 0 24 6 2 DWG 2 FVR002C9S 7UX 0 24 6 0 45 11 5 TERMINAL M3 5 D1 0 24 6 2 0 24 6 2 D D2 0 24 6 2 4 65 118 4 21 107...

Page 12: ...t temperature should be be tween 10 C and 50 C Install the drive in the environment of pollution degree 2 If environment is pollu tion degree 3 or 4 the drive should be installed in a cabinet of IP54...

Page 13: ...of over voltage category II If the power supply is over voltage category III place the devices to limit the over voltage below 2 5kV Required for CE Certification 5 Reinstall the cover Connect the ha...

Page 14: ...on the keypad panel The RUN STOP function of the drive is controlled by the RUN STOP keys on the keypad panel PE terminal blocks for the drive and motor should be provided in the cabinet in which the...

Page 15: ...an external potentiometer together with the potentiometer on the keypad panel may result in damage to the drive PE terminal blocks for the drive and motor should be provided in the cabinet in which th...

Page 16: ...RF25 FVRF50 FVRF001 FVRF002 C9S 7UX C9S 7UX C9S 7UX C9S 7UX C9S 7UX Output rated capacity kVA 0 27 0 5 0 87 1 5 2 7 Applicable wire size Main circuit 14 12 AWG Contol circuit 24 MCCB 6 10 16 20 ELCB 6...

Page 17: ...Command Input Terminal Forward direction operation takes place when FWD CM is closed Drive decelerates and stops when FWD CM is opened REV Reverse Stop Command Input Terminal Reverse direction operati...

Page 18: ...t current Two DC voltmeters internal resistance of 10K ohm or greater can be connected In case of DC ammeter 1mA full scale it is necessary to add series resistance of 10K ohm 1 2W This output is a pu...

Page 19: ...rmed by turning the potentiometer control knob on the keypad panel Turn the potentiometer control knob clockwise to increase fre quency Frequency setting by digital signal F01 0 With the function F01...

Page 20: ...Function Code setting 1 F 0 1 0 2 0 2 0 F 0 1 1 3 F 0 1 0 4 0 2 1 F 0 1 1 C92 07 The frequency setting rate of change increases when FUNC DATA key and UP DOWN keys are pressed simultaneously F RUN ST...

Page 21: ...cy current voltage etc If a fault occurs the causes of the problem will be displayed as a code PROGRAM key RESET key Normal mode or program setting mode select key If a fault occurs this key is used t...

Page 22: ...0 2 UP DOWN Press UP key or DOWN key to select function code F 0 1 3 FUNC DATA Press this key to display function code 1 4 UP DOWN Press UP key or DOWN key to change function code data 1 5 FUNC DATA...

Page 23: ...F05 Acceleration TIme 0 0 60s 0 0 setting 0 01s s 0 1 6 0s Yes F06 Deceleration Time 0 0 60s 0 0 setting 0 01s s 0 1 6 0s Yes F07 Torque Boost 0 31 code 13 Yes F08 Electronic Thermal Overload Relay Op...

Page 24: ...2 0 120 Hz Hz 1 0 Yes F23 Jump Frequency 3 0 120 Hz Hz 1 0 Yes F24 High Limiter 0 100 1 100 Yes F25 Low Limiter 0 100 1 0 Yes F26 Bias Setting 0 100 1 0 Yes F27 THR Terminal Function 0 External alarm...

Page 25: ...equency Sets the base frequency the frequency which is the divergent point of the specified torque characteristics and the specified output characteristics 5 0 Frequency can be set in increments of 1...

Page 26: ...standard 4 pole motor 2 Active electronic thermal overload relay protection For a Fuji FV motor F 0 9 Electronic Thermal Overload Relay Level Sets the operation level for the electronic thermal overlo...

Page 27: ...or a forced air cooled motor _ _ 2 110 100 90 80 70 60 50 40 30 20 10 0 0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 0 Drive frequency Hz Setting value Continuously allowable current 105 30 110 100 90 80 70 60 50...

Page 28: ...lows F 1 1 Gain for Frequency Setting Signal Outputs a frequency which is a proportional ratio of the analog frequency setting Selects an analog input signal level when F O 1 is _ _ 1 0 Maximum freque...

Page 29: ...e procedure for displaying the data is as follows The information for any new trip will be stored in the area for the information for the latest trip shown above each trip history will be removed down...

Page 30: ...been tripped can be set 0 The number of retry times is fixed at 5 Retry takes place in 0 5s after trip 1 Note that the retry takes place only in the case where the drive is tripped due to overcurrent...

Page 31: ...percentage of the maximum frequency in increments of 1 within a range of 0 to 100 1 0 0 F 2 7 THR Terminal Function This function enables terminal THR to be used for two different functions by changin...

Page 32: ...ve operation Note1 X1 or X2 terminal is selected via THR BX terminal function change F27 F28 Note 2 In selecting THR BX terminal function F27 F28 individual setting is possible Speed 0 Frequency setti...

Page 33: ...at full scale 9 9 Approximate DC 10 3V at full scale Note The FM terminal output is a pulse output of which frequency is constant 38 1 Hz and duty is variable F 3 3 FM Terminal Function Selection Wit...

Page 34: ...ure rise of cooling element and stops drive OH1 Yes External Alarm Input Stops drive by input of an external signal OH2 Yes Electronic Thermal Overload Detects overload of motor and stops drive OL Yes...

Page 35: ...ace ment of the entire drive Warranty period is 12 months after installa tion or 18 months after shipment from the Company whichever occurs first Before calling the number at left to deter mine warran...

Page 36: ...Other Equipment on Same Power Yes No If Yes what Line Reactor on Input Yes No Input Starter Yes No Output Starter Yes No Motor Overloads Yes No Control Terminals Used circle if used THR X1 X2 X3 30A...

Page 37: ...to the drive system It is essential that precautions are taken both at the design stage and at the time of installation to prevent radio fre quency interference RFI from the drive system affecting sen...

Page 38: ...he drives may be mounted on top of the filter using the integral fixing positions the intention being that valuable space inside wiring cabinets may be saved Refer to Fig 1 and Table 1 Filter Applied...

Page 39: ...ter foot mounted Drive 1 turn Ferrite ring L N PE L N L1 L2 U V W Enclosure E Screen Basic Standards EN55011 Class B Screening must be electrically continuous and earthed at the enclosure and the moto...

Page 40: ...FILTER Power supply single phase 220 240V 50 60 HZ L N PE L N L1 L2 U V W 30C 30B 30A 13 12 11 Alarm Signal 3 2 1 Frequency setting Potentiometer FM CM CM FWD REV THR EX RST Control input M E Armored...

Page 41: ...41 FVR C9S 7UX...

Page 42: ...he following standard s Immunity EN50082 2 Generic immunity standard Part 2 Industrial Environment Emission EN50081 1 Generic emission standard Part 1 residential commercial and light industrial and c...

Page 43: ...ow voltage requirements of the following standard s DIN VDEO160 1988 Category Overvoltage category II Pollution degree 2 and conforms to the protection requirements of Council Directive 73 23 EEC rela...

Page 44: ...44 FVR C9S 7UX INR Si47 0459 b E Printed in Japan GE Fuji Drives USA Inc 1501 Roanoke Blvd Suite 435 Salem VA 24153 1 800 543 6196 Internet Address http www ge com...

Reviews: