50
Hold mode selection
What is "Hold mode selection"?
This function allows you to switch over between the peak hold mode and sample hold
mode manually or by external input.
When By menu is selected, the mode set by the Hold Mode is effective.
When By signal is selected, set IN-100's external input/output terminal No. 15 MODE to
OFF (HIGH) to set the sample hold mode and to ON (LOW) to set the peak hold mode.
The peak hold mode holds and judges the maximum value of load from the beginning of
load measurement to end signal.
The sample hold mode holds and judges the instantaneous load when end signal.
How to set
1. Press MENU key.
2. Use
⋀
⋁
key to select
Hold Function Setting
.
3. Press SET key.
4. Use
⋀
⋁
key to select
Hold mode selection
.
5. Press SET key.
6. Use
⋀
⋁
key to select By menu or By signal. (default: By menu)
7. Press SET key and confirm the cursor has turned green.
8. Press SET key again to complete this operation.