22 / 34
ba_7-1-120/11E/0318
6.2.2 Command BR
<id>BR<parameter><CR>
Select baud rate
Access:
Read / write.
Description:
The command BR is used to select the required baud rate.
Parameter description:
Parameter
Description
12
1200baud (8n1)
24
2400baud (8n1)
48
4800baud (8n1)
96
9600baud (8n1)
192
19200baud (8n1)
384
38400baud (8n1)
576
57600baud (8n1)
1152
115200baud (8n1)
Value range:
12 / 24 / 48 / 96 / 192 / 384 / 576 / 1152
Initial value:
96
6.2.3 Command DC
<id>DC<parameter><CR> Mode of calculation for twilight
Access:
Read/ write.
Description:
The mode of calculation for twilight is stated by command DC. The
twilight is calculated from the 4 brightness values, depending on
direction. Here, one can select between sum and mean value.
Parameter description:
0: Twilight corresponds to the sum of the 4 brightness values
1: Twilight corresponds to the mean value of the 4 brightness values
value rang:
0...1
Initial value:
0
6.2.4 Command DO
<id>DO<parameter><CR> North correction of wind direction
Access:
Read / write.
Description:
The command DO is used to specify an offset for the wind direction
in °. This brings about correction to the north for the Weather Station.
Value range:
0…360
Initial value:
0