Modbus Adress 7 (value 1 + 2 + 4 = 7)
DIP
Switch
1
2
3
4
5
6
Position
1
1
1
0
0
0
Modbus Adress 20 (value 4 + 16 = 20)
DIP
Switch
1
2
3
4
5
6
Position
0
0
1
0
1
0
Terminating res-
istors - explana-
tion of symbols
Inverter in the system
e.g. Fronius Symo
Meter - Fronius Smart Meter
Terminating resistor is integrated in the meter.
Modbus RTU slave
e.g. Fronius Ohmpilot, Fronius Solar Battery, etc.
Termination resistance
R 120 Ohm
Terminating Res-
istors
The system might work without terminating resistors. Due to interferences, the
use of terminating resistors according to the following schemes are recommen-
ded.
Activate the Fronius Smart Meter ter-
minating resistor (R 120 Ohm) by
switching pin 7 to ON (1).