Display of version number and serial number of the PC boards installed in the inverter (e.g.,
for service purposes)
Grid frequency limits:
FILmax - upper inner grid frequency value in Hz (Hertz)
FILmin - lower inner grid frequency value in Hz (Hertz)
FOLmax - upper outer grid frequency value in Hz (Hertz)
FOLmin - lower outer grid frequency value in Hz (Hertz)
Q-Mode:
Indicates the current reactive power setting on the inverter (e.g.
OFF, Q/P...)
AC power limit, includ-
ing indication of SoftS-
tart and/or AC grid
frequency derating:
Max P AC - maximum output power, which can be changed with
the ‘Manual Power Reduction’ function
GPIS - Gradual Power Incrementation at Startup - indicates (%/
sec) whether the SoftStart function is activated on the inverter
GFDPRe - Grid Frequency Dependent Power Reduction enable
limit - displays the set grid frequency value in Hz (Hertz) from
when a power reduction occurs
GFDPRv - Grid Frequency Dependent Power Reduction derat-
ing gradient - displays the set grid frequency value in %/Hz to
indicate the extent of the power reduction
AC voltage derating:
GVDPRe - Grid Voltage Depending Power Reduction enable
limit - threshold in V from which the voltage-dependent power
reduction starts
GVDPRv - Grid Voltage Depending Power Reduction derating
gradient - reduction gradient in %/V at which the power is re-
duced
Message - shows whether the dispatch of an info message via
Fronius Solar Net is activated
Display range
Display/Display Software/Integrity Checksum/Memory Card/
Memory Card #1/Power Stage/Power Stage Software/EMI Fil-
ter/Power Stage #3/Power Stage #4