If a curve is selected that requires an
external temperature sensor, a mes-
sage appears.
1
Confirm the message by pressing
the "Pause/Start" button.
Equalizing
charge
Equalising charge
OFF
-
No equalizing charge takes place.
delay
-
If the battery remains connected to the battery charger for the duration of
the set equalizing charge delay ("equalize charge delay"), a special form of
charging takes place. This prevents acid stratification.
-
The parameters for current (amperes/100 ampere hours), voltage (volts/cell)
and duration of the equalizing charge can be changed.
Weekday
-
Specification of the day of the week on which the equalizing charge is to take
place.
-
The parameters for current (amperes/100 ampere hours), voltage (volts/cell)
and duration of the equalizing charge can be changed.
Manual
-
An equalizing charge can be activated manually by pressing a button on the
display.
-
The equalizing charge starts after the set delay with the set parameters.
-
The parameters for current (amperes/100 ampere hours), voltage (volts/cell)
and duration of the equalizing charge can be changed.
-
This function is only available for Pb-WET curves.
If a setting for the equalizing charge is activated, a symbol next to the set
ampere hours/the set charging time in the home screen indicates whether the
equalizing charge is being carried out or can be started.