Permitted cables
for the data
communication
area
Cables with the following design can be connected to the terminals of the invert-
er:
-
Copper: round, solid
-
Copper: round, fine-stranded
IMPORTANT!
Connect the individual conductors to an appropriate ferrule if several individual
conductors are connected to one input of the push-in terminals.
WSD connections with push-in terminal
Dis-
tance
max.
Stripping
length
Solid
Fine-stran-
ded
Fine-stran-
ded with fer-
rules with
collar
Fine-stran-
ded with fer-
rules without
collar
Cable re-
commenda-
tion
100 m
109 yd
10 mm
0.39 inch
0.14 -
1.5 mm
2
AWG 26-16
0.14 -
1.5 mm
2
AWG 26-16
0.14-1 mm
2
AWG 26-18
0.14 -
1.5 mm
2
AWG 26-16
min. CAT 5
UTP (unshiel-
ded twisted
pair)
Modbus connections with push-in terminal
Dis-
tance
max.
Stripping
length
Solid
Fine-stran-
ded
Fine-stran-
ded with fer-
rules with
collar
Fine-stran-
ded with fer-
rules without
collar
Cable re-
commenda-
tion
300 m
328 yd
10 mm
0.39 inch
0.14 -
1.5 mm
2
AWG 26-16
0.14 -
1.5 mm
2
AWG 26-16
0.14-1 mm
2
AWG 26-18
0.14 -
1.5 mm
2
AWG 26-16
min. CAT 5
STP (shiel-
ded twisted
pair)
IO connections with push-in terminal
Dis-
tance
max.
Stripping
length
Solid
Fine-stran-
ded
Fine-stran-
ded with fer-
rules with
collar
Fine-stran-
ded with fer-
rules without
collar
Cable re-
commenda-
tion
30 m
32 yd
10 mm
0.39 inch
0.14 -
1.5 mm
2
AWG 26-16
0.14 -
1.5 mm
2
AWG 26-16
0.14-1 mm
2
AWG 26-18
0.14 -
1.5 mm
2
AWG 26-16
Single con-
ductor pos-
sible
LAN connections
Fronius recommends using at least CAT 5 STP (shielded twisted pair) cables and a maximum dis-
tance of 100 m (109 yd).
Cross section of
the AC cable
For a standard M32 metric screw joint with a reducer:
Cable diameter from 7-15 mm
When using an M32 metric screw joint (reducer removed):
cable diameter from 11-21 mm
62
Summary of Contents for Primo GEN24 3.0
Page 2: ......
Page 12: ...12...
Page 13: ...General information 13...
Page 14: ...14...
Page 34: ...34...
Page 35: ...Backup power variant PV Point OP 35...
Page 36: ...36...
Page 38: ...38...
Page 39: ...Backup power variant Full Backup 39...
Page 40: ...40...
Page 48: ...48...
Page 49: ...Installation 49...
Page 50: ...50...
Page 57: ...Do not install the inverter on the ceiling 57 EN...
Page 101: ...Settings user interface of the in verter 101...
Page 102: ...102...
Page 132: ...132...
Page 133: ...Options 133...
Page 134: ...134...
Page 144: ...144...
Page 145: ...Appendix 145...
Page 146: ...146...
Page 172: ...172...
Page 173: ...Circuit diagrams 173...
Page 174: ...174...
Page 175: ...Circuit Diagram PV Point OP Circuit Diagram 175 EN...
Page 176: ...Fronius Primo GEN24 and BYD Battery Box Premium HV Circuit Diagram 176...
Page 179: ...Automatic switch to backup power 1 pin double separation e g Austria Circuit Diagram 179 EN...
Page 180: ...Automatic switch to backup power 1 pin single separation e g Australia Circuit Diagram 180...
Page 181: ...Automatic switch to backup power 2 pin double separation e g Germany Circuit Diagram 181 EN...
Page 182: ...Automatic switch to backup power 2 pin single separation e g France Spain Circuit Diagram 182...
Page 183: ...Automatic switch to backup power 2 pin double separation e g UK Circuit Diagram 183 EN...
Page 185: ...Fronius Primo GEN24 with Enwitec Box Circuit Diagram 185 EN...
Page 186: ...Wiring diagram surge protective device SPD Circuit Diagram 186...
Page 187: ...Dimensions of the inverter 187...
Page 188: ...188...
Page 189: ...Fronius Primo GEN24 3 6 kW Fronius Primo GEN24 3 6 kW 189 EN...
Page 190: ...190...
Page 191: ...191 EN...
Page 192: ......