Connecting solar module strings to the inverter
General com-
ments regarding
solar modules
To enable suitable solar modules to be chosen and to use the inverter as efficiently as
possible, it is important to bear the following points in mind:
-
If insolation is constant and the temperature is falling, the open circuit voltage of the
solar modules will increase. The open circuit voltage must not exceed the maximum
permissible system voltage. If the open circuit voltage exceeds the specified values,
the inverter will be destroyed and no warranty claims will be entertained.
-
The temperature coefficients on the data sheet of the solar modules must be
observed.
-
Exact values for sizing the solar modules can be obtained using suitable calculation
tools, such as the
.
IMPORTANT!
Before connecting up the solar modules, check that the voltage for the solar modules
specified by the manufacturer corresponds to the actual measured voltage.
IMPORTANT!
The solar modules connected to the
inverter must comply with the IEC 61730
Class A standard.
IMPORTANT!
Solar module strings must not be earthed.
Safety
WARNING!
Incorrect operation or poorly executed work can cause serious injury or damage.
Commissioning as well as maintenance and service work in the power module of the
inverter must only be carried out by service personnel trained by Fronius and only within
the scope of the respective technical regulations. Read the Installation and Operating
Instructions before installing and commissioning the equipment.
WARNING!
An electric shock can be fatal.
Danger due to grid voltage and DC voltage from solar modules that are exposed to light.
▶
Ensure that the AC and DC side of the inverter are de-energised before carrying out
any connection/maintenance or service tasks.
▶
Only an authorised electrical engineer is permitted to connect this equipment to the
public grid.
61
EN
Summary of Contents for Primo GEN24 3.0 Plus
Page 2: ......
Page 11: ...General information 11...
Page 12: ...12...
Page 31: ...Backup power variant PV Point OP 31...
Page 32: ...32...
Page 34: ...34...
Page 35: ...Backup power variant Full Backup 35...
Page 36: ...36...
Page 43: ...Installation 43...
Page 44: ...44...
Page 50: ...Do not install the inverter on the ceiling 50...
Page 84: ...84...
Page 90: ...90...
Page 91: ...Settings website of the inverter 91...
Page 92: ...92...
Page 110: ...I O power man agement settings 4 relays 110...
Page 112: ...I O power man agement settings 3 relays 112...
Page 114: ...I O power man agement settings 2 relays 114...
Page 118: ...118...
Page 119: ...Options 119...
Page 120: ...120...
Page 129: ...Appendix 129...
Page 130: ...130...
Page 143: ...Circuit diagrams 143...
Page 144: ...144...
Page 145: ...Circuit Diagram PV Point OP Circuit Diagram 145 EN...
Page 146: ...Fronius Primo GEN24 and BYD Battery Box Premium HV Circuit Diagram 146...
Page 147: ...Automatic switch to backup power 1 pin double separation e g Austria Circuit Diagram 147 EN...
Page 148: ...Automatic switch to backup power 1 pin single separation e g Australia Circuit Diagram 148...
Page 149: ...Automatic switch to backup power 2 pin double separation e g Germany Circuit Diagram 149 EN...
Page 150: ...Automatic switch to backup power 2 pin single separation e g France Spain Circuit Diagram 150...
Page 151: ...Automatic switch to backup power 2 pin double separation e g UK Circuit Diagram 151 EN...
Page 153: ...Fronius Primo GEN24 with Enwitec Box Circuit Diagram 153 EN...
Page 154: ...Wiring diagram surge protective device SPD Circuit Diagram 154...
Page 155: ...Dimensions of the inverter 155...
Page 156: ...156...
Page 157: ...Fronius Primo GEN24 3 6 kW Fronius Primo GEN24 3 6 kW 157 EN...
Page 158: ...158...
Page 159: ...159 EN...