138
Class 5 status
codes
Class 5 status codes generally do not im-
pair the operation of feeding power into the
grid. They will be displayed until the status
code is acknowledged by pressing a key
(the inverter, however, continues working
normally in the background).
-
press any key
-
error message disappears
Description
The inverter stops feeding power into the grid, the display
shows a critical error via a red Operating Status LED.
Remedy
Insert new fuse for the solar module ground so that the solar
modules are grounded at the negative or positive pole.
Fault is rectified automatically
If this status code keeps recurring, contact your system installer
474
Short circuit between DC connection and ground (external insulation fault)
High ohm resistor for solar module ground is defective
Description
The inverter stops feeding power into the grid, the display
shows a critical error via a red Operating Status LED.
Remedy
Insert new high ohm resistor for solar module ground.
Remedy external insulation fault
Fault is rectified automatically
If this status code keeps recurring, contact your system installer
475
DC insulation fault
The insulation value of the DC terminals to the protective earth (PE) is
≤
500 kilohms
Description
The inverter interrupts feed-in operation
Remedy
Correct insulation fault
502
DC insulation fault
Description
While automatically measuring the insulation, the inverter has
detected an insulation fault to the ground.
Remedy
Check the insulation of your photovoltaic system
The status code reappears: contact your system installer
504
No Solar Net communication possible
Description
Inverter address issued twice.
Remedy
Change inverter address (section: ‘The Setup menu’)
Summary of Contents for IG Plus 100 V-1
Page 2: ...0...
Page 4: ...2...
Page 10: ...8...
Page 16: ...14...
Page 17: ...General Information...
Page 18: ......
Page 20: ...18 Safety symbols Risk of serious injury and damage due to incorrect operation...
Page 24: ...22...
Page 25: ...Installation and Startup...
Page 26: ......
Page 76: ...74 1 2 6 x 18...
Page 80: ...78 Closing Fronius IG Plus Closing Fronius IG Plus 1 1 3 2 1 1 2 3 2 4 1 3...
Page 89: ...Operation...
Page 90: ......
Page 126: ...124...
Page 127: ...Troubleshooting and Maintenance...
Page 128: ......
Page 146: ...144 Disconnect DC wire Disconnect AC wire 8 9...
Page 150: ...148...
Page 151: ...Appendix...
Page 152: ......
Page 164: ...162...
Page 165: ...163 g...
Page 167: ...165 g...