90
Class 5 status
codes
Class 5 status codes generally do not im-
pair the operation of feeding power into the
grid. They will be displayed until the service
code is acknowledged by pressing a key
(the inverter, however, continues working
normally in the background).
-
press any key
-
error message disappears
446
Internal communication error with the NL-MON plug-in card
Description
The inverter will automatically attempt to connect again and, if
possible, resume feeding power into the grid
Remedy
Check grid connections and fuses;
If status code persists: Contact a Fronius-trained service tech-
nician
447
GFDI stopped grid monitoring
Description
If it is possible, your inverter will resume the power feeding op-
eration after successfully completing another attempt to con-
nect
Remedy
If status code persists: Contact a Fronius-trained service tech-
nician
448
The neutral conductor N is not connected
Description
The inverter disconnects from the grid for safety reasons.
Remedy
If status code persists: Contact a Fronius-trained service tech-
nician
501
One of the two fans is defective
Description
Low power generation because the temperature in the unit is
too high.
Remedy
If status code persists: Contact a Fronius-trained service tech-
nician
504
No Solar Net communication possible
Description
Inverter address issued twice.
Remedy
Change inverter address (section: ‘The setup menu’)
Summary of Contents for IG 2000
Page 2: ...0...
Page 4: ...2...
Page 6: ...4...
Page 10: ...8...
Page 15: ...General Information...
Page 16: ......
Page 21: ...Installation and Startup...
Page 22: ......
Page 50: ...48...
Page 51: ...Operation...
Page 52: ......
Page 80: ...78...
Page 81: ...Troubleshooting and Maintenance...
Page 82: ......
Page 95: ...Appendix...
Page 96: ......
Page 113: ...111 EN US...
Page 114: ...112...
Page 115: ...113 EN US...