Field adjustable
trip points
Relevant stan-
dards and direc-
tives
Field adjustable trip points
208 V
240 V
Nominal AC output voltage,
Line-to-Line, [V]
208
240
Operating AC voltage range default,
Line-to-Line, [V]
183-229
212-264
Adjustment range for voltage,
Line-to-Line, [V]
180-240
180-270
Voltage trip limit accuracy
Line-to-Line,
[% of nominal value]
± 1,5
± 1,5
Nominal output frequency [Hz]
60
60
Operating frequency range [Hz]
59.3-60.5
59.3-60.5
Adjustment range for frequency [Hz]
57.0-60.5
57.0-60.5
Frequency trip limit accuracy, [Hz]
± 0,02
± 0,02
Reconnect time, [s]
305
305
Adjustment range for reconnect time, [s]
1-999
1-999
Operating AC voltage range
Line-to-Neutral, [V]
106 - 132
106 - 132
Adjustment range for voltage
Line-to-Neutral, [V]
60 - 144
60 - 144
Voltage trip limit accuracy
Line-to-Neutral,
[% of nominal value]
± 1,5
± 1,5
-
UL 1741
-
IEEE 1547
-
IEEE 1547.1
-
ANSI/IEEE C62.41
-
FCC Part 15 A & B
-
NEC Article 690
-
C22. 2 No. 107.1-01
(September 2001)