Fault Ride Through:
Status – Default setting: OFF
If the function is activated, the inverter does not switch
off immediately in the event of a short-term AC voltage
dip (outside of the limits specified by the grid supplier),
but instead continues to feed in power for a defined
period.
DB min – Default setting: 90%
"Dead Band Minimum" setting in per cent
DB max - Default setting: 120%
"Dead Band Maximum" setting in per cent
k-Fac. - Default setting: 0
Version
Displays the version and serial numbers of the PC boards in the inverter (e.g. for
service purposes)