
Energy Manager:
E-Manager:
Further details on the "Energy Manager" function may be
found in the "Energy Manager" section.
Relay test
Function test to determine whether the floating switch contact switches
Switch-on point
(only if "Energy Manager" function is activated)
for setting the effective power limit beyond which the floating switch contact is
switched on
Factory setting
1000 W
Setting range
Set switch-off point up to the maximum nominal output
of the inverter (W or kW)
Switch-off point
(only if "Energy Manager" function is activated)
for setting the effective power limit beyond which the floating switch contact is
switched off
Factory setting
500
Setting range
0 to the set switch-on point of the inverter (W or kW)
Energy Manager
(under "Relay"
menu item)
The "Energy Manager" function can be used to activate the floating switch con-
tact in such a way that it functions as an actuator.
Thus, a load that is connected to the floating switch contact can be controlled by
specifying a switch-on or switch-off point that depends on the power of feeding
in.
The floating switch contact is automatically switched off:
-
If the inverter is not feeding any power into the grid
-
If the inverter is manually switched to Standby mode
-
If the effective power is set to < 10% of the rated power
To activate the "Energy Manager" function, select "E-Manager" and press the
"Enter" key.
When the "Energy Manager" function is running, the "Energy Manager" symbol
will appear in the top left corner of the display:
When the floating NO contact is off (open contact)
When the floating NO contact is on (closed contact)
To deactivate the "Energy Manager" function, select a different function and
press the "Enter" key.
Notes on setting up the switch-on and switch-off points
The interface of the energy management relay always uses the output power of
the inverter as a reference point, although this will not necessarily match what is
generated by the PV system in the case of the hybrid system.
If the difference between the switch-on and switch-off points is too small, or if
there are fluctuations in effective power, the result may be multiple switching
cycles
To avoid frequent switching on and off, the difference between the switch-on and
switch-off points should be at least 100 - 200 W.
56
Summary of Contents for Energy Package
Page 2: ......
Page 10: ...10...
Page 11: ...General information 11...
Page 12: ...12...
Page 37: ...Operation 37...
Page 38: ...38...
Page 69: ...Fronius system monitoring 69...
Page 70: ...70...
Page 82: ...82...
Page 83: ...Current data services and settings offered by Fronius system monitor ing 83...
Page 84: ...84...
Page 121: ...Troubleshooting and maintenance 121...
Page 122: ...122...
Page 136: ...136...
Page 137: ...Appendix 137...
Page 138: ...138...
Page 145: ...145 EN...
Page 146: ...146...
Page 147: ...147 EN...
Page 148: ......