Technical data
Fronius Symo Hybrid
3.0-3-S
4.0-3-S
5.0-3-S
Input data
PV input power
5 kW
6.5 kW
8 kW
MPP voltage range
190 - 800 V DC
250 - 800 V DC
315 - 800 V DC
Max. input voltage
(at 1000 W/m²/ -10 °C in an open cir-
cuit)
1000 V DC
Start-up input voltage for feed-in
200 V
Nominal input voltage
595 V
Min. input voltage
150 V DC
Max. input current
1 x 16.0 A
Max. short circuit current of PV mod-
ules (I
SC PV
)
24.0 A
Number of MPP trackers
1
Number of DC connections
2
Battery input
Max. output power to battery
Depending on the connected battery
Max. input power from battery
Depending on the connected battery
Output data
Nominal output power (P
nom
)
3000 W
4000 W
5000 W
Max. output power
3000 W
4000 W
5000 W
Rated apparent power
3000 VA
4000 VA
5000 VA
Nominal grid voltage
3~ EN 400/230 V3~ EN 380/220 V (+20% / -30%)
Max. output current
8.3 A
8.3 A
8.3 A
Frequency (frequency range)
50 Hz / 60 Hz (45 - 65 Hz)
Total harmonic distortion
< 3 %
Power factor (cos phi)
0.85 - 1 ind./cap.
2)
Current (inrush)
6)
38 A / 2 ms
Max. output overcurrent protection
25 A
General data
Max. efficiency (PV - grid)
97.5 %
97.6
Max. efficiency (PV - battery - grid)
> 90 %
> 90 %
> 90 %
European efficiency (PV - grid)
95.2 %
95.7 %
96 %
Cooling
Controlled forced-air ventilation
Protection class
IP 65
Dimensions h x w x d
645 x 431 x 204 mm
Weight
22 kg
139
EN
Summary of Contents for Energy Package
Page 2: ......
Page 10: ...10...
Page 11: ...General information 11...
Page 12: ...12...
Page 37: ...Operation 37...
Page 38: ...38...
Page 69: ...Fronius system monitoring 69...
Page 70: ...70...
Page 82: ...82...
Page 83: ...Current data services and settings offered by Fronius system monitor ing 83...
Page 84: ...84...
Page 121: ...Troubleshooting and maintenance 121...
Page 122: ...122...
Page 136: ...136...
Page 137: ...Appendix 137...
Page 138: ...138...
Page 145: ...145 EN...
Page 146: ...146...
Page 147: ...147 EN...
Page 148: ......