Status codes –
Class 6
Some of the class 6 status codes necessitate intervention by a Fronius-trained
service engineer.
Code
Description
Behaviour
Remedy
601
CAN bus is full
The inverter is not feed-
ing any energy into the
grid.
Update inverter firm-
ware; *)
603
DC module temperature sensor
faulty
The inverter will auto-
matically attempt to
connect again and, if
possible, will resume
feeding energy into the
grid.
*)
608
Functional incompatibility (one or
more PC boards in the inverter are
not compatible with each other, e.g.
after a PC board has been re-
placed)
The inverter is not feed-
ing any energy into the
grid.
Update inverter firm-
ware; *)
*) If the status code is displayed all the time: Notify a Fronius-trained service en-
gineer.
**) Fault is rectified automatically. If this status code keeps recurring, contact
your system engineer.
Status codes –
Class 7
Class 7 status codes relate to the control system, the configuration and inverter
data recording, and may directly or indirectly affect the process of feeding en-
ergy into the grid.
Code
Description
Behaviour
Remedy
701 -
715
Provides information
about the internal pro-
cessor status
Warning message on the
display
*)
721
EEPROM has been re-ini-
tialised
Warning message on the
display
Acknowledge status code; *)
722 -
730
Provides information
about the internal pro-
cessor status
Warning message on the
display
*)
746
Error occurred during up-
date process
Warning message on the
display, update process
is interrupted
Wait for 2 minutes, then start
the update again; *)
751
Time lost
Warning message on the
display
Reset time and date on the
inverter; *)
752
Real Time Clock module
communication error
753
Internal error: Real Time
Clock module is in emer-
gency mode
Time may be inaccurate
or lost (feeding energy
into the grid normal)
Reset time and date on the
inverter
754 -
755
Provides information
about the internal pro-
cessor status
Warning message on the
display
*)
129
EN
Summary of Contents for Energy Package
Page 2: ......
Page 10: ...10...
Page 11: ...General information 11...
Page 12: ...12...
Page 37: ...Operation 37...
Page 38: ...38...
Page 69: ...Fronius system monitoring 69...
Page 70: ...70...
Page 82: ...82...
Page 83: ...Current data services and settings offered by Fronius system monitor ing 83...
Page 84: ...84...
Page 121: ...Troubleshooting and maintenance 121...
Page 122: ...122...
Page 136: ...136...
Page 137: ...Appendix 137...
Page 138: ...138...
Page 145: ...145 EN...
Page 146: ...146...
Page 147: ...147 EN...
Page 148: ......