Code
Description
Behaviour
Remedy
143
Emergency power overload Emergency power mode is
interrupted. The inverter
attempts to start emer-
gency power mode three
times; if this is unsuccess-
ful status code 145 is dis-
played
Check emergency power
circuit; if this status code
keeps recurring, contact
your system fitter
144
Emergency power short-
circuit
145
Status code 143 or 144
has occurred more than
three times
Status codes –
Class 3
Class 3 includes status codes that may occur while feeding energy into the grid,
but generally do not cause the process to be interrupted for any length of time.
The inverter disconnects automatically from the grid, the grid is then monitored
as specified and the inverter attempts to resume feeding energy into the grid.
Code
Description
Behaviour
Remedy
301
Overcurrent (AC)
Short-term interruption
while feeding energy into
the grid.
The inverter repeats its
start-up routine.
*)
302
Overcurrent (DC) or battery not
detected
303
DC module overtemperature
(PV)
Short-term interruption
while feeding energy into
the grid.
The inverter repeats its
startup routine.
Purge cooling air
openings and heat
sink; **)
304
AC module overtemperature
305
No power being fed in, despite
closed relays
Short-term interruption
while feeding energy into
the grid.
The inverter repeats its
startup routine.
**)
306
There is not enough PV power
available for feeding energy into
the grid and no power has been
requested from the battery.
Short-term interruption
while feeding energy into
the grid.
The inverter repeats its
startup routine.
Wait for sufficient
insolation; wait for
an energy manage-
ment command;
**)
307
DC low
DC input voltage too low for
feeding energy into the grid
Short-term interruption
while feeding energy into
the grid.
The inverter repeats its
startup routine.
Wait for sufficient
insolation;
**)
IMPORTANT!
Due to the low level of insolation early in the morning and in the evening, the status
codes 306 (Power low) and 307 (DC low) are displayed routinely at these times of day. These status
codes do not indicate any kind of fault.
308
Intermediate circuit voltage too
high
Short-term interruption
while feeding energy into
the grid.
The inverter repeats its
startup routine.
**)
309
PV input voltage too high
124
Summary of Contents for Energy Package
Page 2: ......
Page 10: ...10...
Page 11: ...General information 11...
Page 12: ...12...
Page 37: ...Operation 37...
Page 38: ...38...
Page 69: ...Fronius system monitoring 69...
Page 70: ...70...
Page 82: ...82...
Page 83: ...Current data services and settings offered by Fronius system monitor ing 83...
Page 84: ...84...
Page 121: ...Troubleshooting and maintenance 121...
Page 122: ...122...
Page 136: ...136...
Page 137: ...Appendix 137...
Page 138: ...138...
Page 145: ...145 EN...
Page 146: ...146...
Page 147: ...147 EN...
Page 148: ......