Settings – Energy Manager
Energy manage-
ment
Own consumption optimization
The Fronius hybrid inverter always controls the system by adjusting it in line with
the target value set at the metering point. In the "automatic" operating mode
(factory setting), an adjustment is made to 0 W at the feed-in point (maximum
self-consumption).
The target value also applies if a further source feeds into this metering point.
However, in this case:
-
The Fronius Smart Meter must be installed at the feed-in point
-
It is necessary to activate battery charging by a further producer (see
chapter
The self-consumption optimisation has lower priority than the battery control
specifications.
Own consumption optimization
Option for selecting automatic or manual self-consumption optimisation
Target value at the metering point
If you opt for "manual" under "Own consumption optimization", you can select
the target value at the metering point and choose between "Consumption" and
"Feed-in" here
Backup power
Operating mode
"Automatic" or "Off" can be selected for backup power mode.
The backup power functionality can only be activated once the required IO as-
signments have been configured for backup power. The meter must be installed
at the feed-in point and configured.
Residual battery capacity
Energy is drawn from the battery in grid-connected operation until this residual
battery capacity is reached. In backup power mode without a grid, the battery is
always discharged to the minimum SOC preset by the battery manufacturer.
SOC warning level
A warning is output when the residual capacity of the battery specified here is
reached in backup power mode.
Energy manage-
ment examples
These examples illustrate possible energy flows. Efficiency values have not been
taken into account.
Battery system example
PV system to Fronius Symo Hybrid:
1000 W
Household consumption:
500 W
Target value set at feed-in point:
0 W
Power to the battery:
500 W
103
EN
Summary of Contents for Energy Package
Page 2: ......
Page 10: ...10...
Page 11: ...General information 11...
Page 12: ...12...
Page 37: ...Operation 37...
Page 38: ...38...
Page 69: ...Fronius system monitoring 69...
Page 70: ...70...
Page 82: ...82...
Page 83: ...Current data services and settings offered by Fronius system monitor ing 83...
Page 84: ...84...
Page 121: ...Troubleshooting and maintenance 121...
Page 122: ...122...
Page 136: ...136...
Page 137: ...Appendix 137...
Page 138: ...138...
Page 145: ...145 EN...
Page 146: ...146...
Page 147: ...147 EN...
Page 148: ......