Criteria for select
-
ing the right
string fuses
The following criteria must be met for each solar module string when selecting suitable fus
-
es:
-
I
N
> 1.8 x I
SC
-
I
N
< 2.4 x I
SC
-
V
N
>/= maximum open circuit voltage of pv generator
-
Fuse dimensions: diameter 10 x 38 mm
I
N
Nominal current of fuse
I
SC
Short circuit current for standard test conditions (STC) according to the solar mod
-
ule data sheet
V
N
Rated voltage of fuse
NOTE!
The nominal current rating of the fuse must not exceed the maximum fuse protec
-
tion specified in the data sheet supplied by the solar module manufacturer.
If a maximum fuse protection is not specified, then this information must be requested from
the solar module manufacturer.