The string fuse release current can be set to greater than 15 A if required. However, a
release current of 20 A must not be exceeded.
If the inverter is being operated with an external string collection box, the DC connector
kit 25 (item numbers 42,0201,4479 for DC+ and 42,0201,4480 for DC-) must be used. In
this case the solar modules are externally protected in the string collection box and the
metal bolts should be used in the inverter.
National regulations regarding fuse protection must be observed. The electrical engineer
carrying out the installation is responsible for the correct choice of string fuses.
CAUTION!
Danger due to faulty fuses.
This can result in fire.
▶
Only replace faulty fuses with new ones of the same rating.
The inverter is delivered with metal bolts as standard.
Option DC SPD
DC+ 2.1
DC+ 1.1
DC+ 1.3
DC+ 1.2
DC+ 2.3
DC+ 2.2
DC- 1.2
DC- 1.1
D
C
-
1
.3
D
C
-
2
.1
D
C
-
2
.2
D
C
-
2
.3
Do not remove cover!
Each Terminal: I
max
= 15 A
Permitted cables
AC cables with the following design can be connected to the AC terminals of the inverter:
Cu / Al Cu
-
Copper (Cu) or aluminum (Al): round, solid
-
Copper: round, stranded, up to conductor class 4
AC & DC = copper cables (Cu)
The following wire combinations can be used for wiring.
Select a sufficiently large cable cross-section based on the actual device output!
AWG
roun
d
AWG
stran-
ded
AWG
stranded/round
AWG
round/round
AWG
stranded/stranded
4
2)
6
2)
6/6
4)
6/12
2)
6/14
2)
6/16
3)
8
2)
8
1)
8/10
1)
8/12
1)
8/14
1)
8/12
2)
8/10
2)
8/12
1)
8/14
1)
8/16
3)
35
EN-US
Summary of Contents for 10.0-3 208-240
Page 2: ......
Page 13: ...Preparation 13...
Page 14: ...14...
Page 20: ...1 2 20...
Page 21: ...AC 21...
Page 22: ...22...
Page 31: ...DC 31...
Page 32: ...32...
Page 41: ...Laying Solar Net Cables 41...
Page 42: ...42...
Page 43: ...Data communication Lay data commu nication cables 1 2 3 4 5 22 lbf in 2 5 Nm 6 43 EN US...
Page 45: ...1 2 1 3 TX20 10 6 lbf in 1 2 Nm 1 2 4 5 45 EN US...
Page 46: ...46...
Page 47: ...Finally 47...
Page 48: ...48...
Page 51: ...4 3 in 1 ON OFF Lock 22 1 lbf in 2 5 Nm 2 3 4 51 EN US...
Page 52: ...22 1 lbf in 2 5 Nm 5 6 AC ON 2 ON OFF Lock 1 7 52...
Page 55: ...Options 55...
Page 56: ...56...
Page 62: ...62...
Page 63: ...Care and maintenance 63...
Page 64: ...64...
Page 66: ...66...
Page 67: ...67 EN US...