Assembly | 6
M2250322_en | Installation instructions Wood chip boiler T4e 200-350
37
6.3 Installing the boiler
6.3.1 Levelling the boiler
8x
r
Lift the boiler using an appropriate lifting device
r
Position a Sylomer pad under the boiler base
Ä
Sylomer pads prevent the transmission of noise to the ground
r
Carefully release the lifting device and check that the boiler is level
r
If necessary, level the boiler using load-bearing pads
6.3.2 Installing the stoker unit
r
Remove the pre-installed screws on the boiler connection flange
r
Insert the appropriate pipe (e.g. 1” pipe) into the bracket of the stoker unit and
transport the stoker unit to the boiler
r
Position seal (A) on the connection flange
r
Move the stoker unit towards the boiler and insert into the connection flange at the two
lock bolts (B)
r
Adjust the height using the adjustable base (C) as required
r
Secure the stoker unit to the connection flange using the previously removed screws
r
Remove the bracket. It is no longer needed
r
Assemble the entire discharge system