Setting - WOS
System menu
System
Setting
WOS
WOS start time
Time from which the heat exchanger cleaning system can
be activated.
WOS stop time
Time to which the heat exchanger cleaning system can be
activated.
WOS runtime
Time which the heat exchanger cleaning system is
activated.
WOS in firewood mode runs every
Function in firewood mode:
▪ If the insulated door of the boiler is open, the heat
exchanger cleaning system will run for at least the
duration set under the
“WOS runtime”
parameter,
even if the insulated door is closed sooner.
▪ If the boiler is in “LW Heating” mode, the heat
exchanger cleaning system will be activated after the
set time has elapsed for the duration set under the
“WOS runtime”
parameter.
▪ If the boiler switches to “Slumber” mode, the heat
exchanger cleaning system will be activated after a third
of the time set here has elapsed for the duration set
under the
“WOS runtime”
parameter.
Function in pellet mode:
▪ If the boiler shuts down because of a pellet suction
request, the heat exchanger cleaning system will be
activated in “Cleaning” mode for the duration set under
the
“WOS runtime”
parameter.
WOS monitoring active
YES: A contact switch for monitoring the function of the
heat exchanger cleaning system is installed. “Sensor 2”
port on core module.