Commissioning | 6
M2050222_en | Installation instructions Lambdamat LM 1500 KOM
57
6.1.1 Compressed air cleaner (optional)
If there is a compressed air cleaner installed for the heat exchanger, check the following
settings:
r
Maximum pressure: 4 bar
Ä
Set mechanically on pressure reducer
r
Compressed air monitor setting: 2 bar
Set the following parameters on the mecair controller of the compressed air cleaner:
r
Pulse time: 0.5 secs.
r
Pause time: 999 secs.
NOTICE! If a minimum compressor pressure of 2 bar cannot be established, an
error message will appear on the boiler touchscreen!
6.2 Initial startup
6.2.1 Permitted fuels
Wood chips
Description according to
EN ISO 17225-4
Description
M20
Water content max. 20%
M30
Water content max. 30%
M35
Water content max. 35%
M40
1)
Water content max. 40%
M50
1)
Water content max. 50%
P16S
Main proportion (at least 60% mass portion): 3.15 – 16 mm, max.
length of 45 mm, previously referred to as fine wood chips G30
P31S
Main proportion (at least 60% mass portion): 3.15 – 31.5 mm, max.
length of 150 mm, previously referred to as medium-sized wood
chips G50
from 400 kW:
P45S
Main proportion (at least 60% mass portion): 3.15-45 mm, max.
length of 200 mm, previously referred to as medium-sized wood
chips G50
from 400 kW:
P63
2)
Main proportion (at least 60% mass portion): 3.15–63 mm, max.
length 350 mm, previously referred to as coarse wood chips G100
1. partial load conditions only to a limited extent
2. for hydraulic feeders only
Note on standards
EU:
Fuel as per EN 17225 – Part 4: Wood chips class A1 / P16S-P45S
Additional for
Germany:
Fuel class 4 (§3 of the 1st Federal Emissions Protection Ordinance (BimSchV)
in the last amended version)