Installation | 5
M2050222_en | Installation instructions Lambdamat LM 1500 KOM
41
Insert the following sensors into the respective immersion sleeves:
r
A: Return sensor
r
B: Capillary of high-limit thermostat (STL)
r
C: Sensor of thermal discharge safety device
r
D: Sensor of thermal discharge safety device
r
E: Boiler sensor
r
F: Undergrate temperature sensor
(on same side of boiler as combustion air fan)
r
Fit STL housing to side panel using screws provided
NOTICE! Do not link cable of STL capillary!
5.6.16 Installing the servo-motors
r
Check that the air flaps are at the left stop.
Ä
All air flaps should be closed.
Ä
Where necessary, turn the air flaps to the left stop using pliers.
L
r
Set the direction of rotation of the servo-motor (1) to left (L).
r
Press the unlock key (2) and turn the drive for the shaft to the air duct (3) in an anti-
clockwise direction as far as the stop.