Servicing the system | 5
B1300122_en | Operating instructions Lambdamat LM 800-1000
43
5.5.2 Periodic inspection and cleaning (approx. 1,000 hrs)
For fuels with a low ash content, cleaning and inspection after approx. 1,000 service
hours is usually sufficient (under normal use conditions, approximately every quarter). For
less efficient fuels and fuels with a high ash content (indicated by short emptying intervals
for the ash container), the work should be carried out more frequently accordingly.
WARNING
Inspection and cleaning work on a system which is operational:
Risk of serious injuries from automatic startup of the system and severe burns
from hot parts and the flue gas pipe!
When working on the system:
r
always wear protective gloves
r
only operate the boiler using the handles provided
r
switch off the boiler by tapping “Boiler off” at the mode icon
Ä
The boiler follows the shutdown procedure and switches to “Switched off OFF“
status
r
switch off the main switch and take precautions to prevent accidental switching on
r
allow the boiler to cool off for at least 1 hour
r
once all of the tasks have been completed, turn the main switch back on and switch
the boiler on in the desired mode
Cleaning the ash transfer chamber
"Periodic inspection and cleaning" [
r
Remove the cleaning door at the back of the boiler
r
Check the ash level in the ash transfer chamber and clean using an ash vacuum, if
necessary