26
7425MUM753
Model: CWE-Q
- Use and Maintenance Manual
Rev. 15
7.1
M
INIMUM WATER FLOW
It is recommended to grant a minimum water flow to the chiller in order to avoid
serious damages to the evaporator and to the whole machine (see following table).
Model CWE-Q
041
068
100
140
Minimum water flow [gal/min] 11,2
15,9
25,1
35,2
Minimum water flow [m
3
/h]
2,55
3,6
5,7
8
Check that water temperature difference between inlet and outlet of the chiller is
less than 14.4°F/8°C; higher values could be the symptom of an insufficient water
flow.