OPERATION
Digital Control User Input Configuration
22
The.adjustable.control.dip.switches.are.located.at.the.lower.left.hand.portion.of.the.digital.Smart.Center..The.inputs.are.only.visible.and.accessible.with.the.
front.cover.removed.from.the.PTAC.
Digital Control User Input Configuration
Switch
Description
Function
Factory Setting
Option
1
Emergency.Heat.Override.
for.PZH.Heat.Pump.
Models
Enables.electric.heat.only.operation.in.the.event.of.a.com-
pressor.failure.on.HP.models.
Down.-.Normal.Operation
Up.-.Overrides.compressor.operation..
(PDH.models.only)
2
Wall.Thermostat.Switch
Enables.the.use.of.a.wall.thermostat.or.unit.controls
Down.-.Unit.Controls
Up.-.Enables.Wall.Thermostat.Usage
3
Fan.Cycle.for.Heating
Allows.selection.of.continuous.fan.or.cycling.in.heating.mode.
Not. Applicable
4
Fan.Cycle.for.Cooling
Allows.selection.of.continuous.fan.or.cycling.in.cooling.mode.
Not. Applicable
Not. Applicable
Not. Applicable
5
Setpoint.Switch.1
Allows.the.temperature.setpoint.range.to.be.adjusted.
Down
61ºF-86ºF Up
63ºF-80ºF Down
Up
6
Setpoint.Switch.2
Down
(16ºC-30ºC) Down (18ºC-28ºC)
65ºF-78ºF
(19ºC-26ºC)
68ºF-75ºF
(20ºC-24ºC)
Up
Up
7
Room.Freeze.Protection
Allows.the.unit.to.ensure.the.indoor.room.temperature.does.
not.fall.below.40ºF.even.when.turned.off.
Down.-.Freeze.Protection.Enabled
Up.-.Freeze.Protection.Disabled
FRP028
DIP SWITCH
LOCATION OF
DIP SWITCHES
ON UNIT
1
2
3
4
5
6
7
Freeze guard
Setpoint Limit 2
Setpoint Limit 1
Fan CON/CYC for cooling
Fan CON/CYC for heating
Wall Thermostat enable
Electric heat only (for Heat Pumps)
UP
DOWN
High
Med
Low
Fan
Cool
Heat
Fan Speed
Mode
Temperatu
re
Power
Figure 31
Dip Switches
1.
Emergency Heat Override – Switch 1
In.the.unlikely.event.of.a.compressor.failure.a.heat.pump.unit.may.
be.switched.to.operate.in.only.the.electric.heat.mode.until.repairs.
can.be.made..Moving.Dip.Switch.1.to.‘ON’.
2.
Wall Thermostat Switch 2
In.order.to.enable.the.wall.thermostat.move.Dip.Switch.to.'ON'.
3.
Fan Cycle Control – Switch 3-4
All.PTACs.are.shipped.from.the.factory.with.Dip.Switch.3-4.in.
the.‘OFF’.position...In.this.position.the.cooling.fan.cycle.will.run.
continuously.providing.air.circulation.during.the.warm.months...
The.heating.fan.cycle.is.set.to.'cycle'.on.and.off...The.fan.may.
be.set.to.'continuous'.mode.by.switching.Dip.Switch.3.to.'ON'.
position.
4.
Electronic Temperature Limiting – Switches 5-6
The.digital.control.is.set.from.the.factory.to.allow.a.temperature.
range.between.61°.F.and.86°.F.in.both.heating.and.cooling.
mode..Dip.Switches.5-6.can.be.used.to.set.high.and.low.limits.for.
either.heating.both,.cooling.both.or.both.
From.the.factory.switches.are.in.the.down.'OFF'.position..The.
chart.below.shows.the.available.electronic.limiting.ranges.
5.
Room Freeze Protection – Switch 7
Units.are.shipped.from.the.factory.with.the.room.freeze.protection.
enabled...Room.Freeze.Protection.can.be.switched.off.at.the.
owner’s.preference.by.moving.Dip.Switch.7.to.‘OFF’..This.feature.
will.monitor.the.indoor.room.conditions.and.in.the.event.that.the.
room.falls.below.40°F.the.unit.will.cycle.on.high.fan.with.the.
electric.heater..This.occurs.regardless.of.mode.
Dip Switch Setting
The adjustable control dip switches are located at the lower left hand portion of the digital Smart Center, The inputs are only visible and
accessible with the front cover removed from the PTAC,
Dip Switch Setting
1.
Emergency Heat Override – Switch 1 In the unlikely event of a compressor failure a heat pump unit may be switched to operate in
only the electric heat mode until repairs can be made. Moving Dip Switch 1 to ‘ON’
2.
Wall Thermostat Switch 2
In order to enable the wall thermostat move Dip Switch to ‘ON’
3.
Fan Cycle Control – Switch 3-4 All PTACs are shipped from the factory with Dip Switch 3-4 in the ‘OFF’ position In this position
the cooling fan cycle will run continuously providing air circulation during the warm months. The heating fan cycle is set to ‘cycle’ on and off
The fan may be set to ‘continuous’ mode by switching Dip Switch 3 to ‘ON’ position.
4.
Electronic Temperature Limiting – Switches 5-6 The digital control is set from the factory to allow a temperature range between
61° F and 86° F in both heating and cooling mode Dip Switches 5-6 can be used to set high and low limits for either heating both, cooling
both or both.
From the factory switches are in the down ‘OFF’ position The chart below shows the available electronic limiting ranges.
5.
Room Freeze Protection – Switch 7 Units are shipped from the factory with the room freeze protection enabled Room Freeze
Protection can be switched off at the owner’s preference by moving Dip Switch 7 to ‘OFF’ This feature will monitor the indoor room
conditions and in the event that the room falls below 40°F the unit will cycle on high fan with the electric heater
This occurs regardless
of mode.
Summary of Contents for ZONEAIRE SELECT PZE07K3SA
Page 47: ...47 COMPONENT TESTING Electrical ...
Page 48: ...48 COMPONENT TESTING Electrical ...
Page 61: ...61 TROUBLESHOOTING MalfunctionAnalysis ...
Page 62: ...62 TROUBLESHOOTING Malfunction Analysis ...
Page 63: ...63 TROUBLESHOOTING Malfunction Analysis ...
Page 64: ...64 TROUBLESHOOTING Malfunction Analysis ...
Page 66: ...66 TROUBLESHOOTING HeatPump Figure 702 ...
Page 67: ...67 WIRING DIAGRAMS RemoteWallThermostatWiringDiagram CoolWithElectricHeat Figure 801 ...
Page 68: ...68 WIRING DIAGRAMS Remote Wall Thermostat Wiring Diagram HeatPumpWithElectricHeat Figure 802 ...
Page 69: ...69 Figure 803 WIRING DIAGRAMS ...
Page 71: ...71 PARTS CATALOG PZE Figure 901 ...