151
PB
COMPONENTS TESTING
Thermistor Values
All thermistors in the VRP units have
a 10k ohm Resistence at 77° F.
The chart below shows the value vs.
temperature
If the sensor reads O/L (open) or 0
OHM (short) it is a bad sensor and
should be replaced.
If the sensors OHM value equates
to a temperature that is incorrect,
i.e. room temperature is 65 ° but the
sensor reads 6 OHM (97°), then the
sensor is out of calibration and needs
to be replaced.
TEMP
RESISTENCE (K Ohms)
RESISTANCE
TOLERANCE %
MAX
F
MIN
MIN
MAX
CENTR
-25
210.889
225.548
240.224
6.50
6.51
178.952
-20
190.889
202.825
6.25
6.25
-15
151.591
161.325
171.059
6.03
6.03
-10
128.434
144.292
5.81
136.363
5.81
108.886
-5
115.340
121.794
5.60
5.60
0
92.411
97.662
102.912
5.38
5.38
5
78.541
82.812
87.083
5.16
5.16
10
66.866
70.339
73.812
4.94
4.94
15
57.039
59.864
62.688
4.72
4.72
20
48.763
51.060
53.357
4.50
4.50
25
41.786
43.654
45.523
4.28
4.28
30
35.896
37.415
38.934
4.06
4.06
31
34.832
36.290
37.747
4.02
4.02
32
33.803
35.202
36.601
3.97
3.97
33
32.808
34.150
35.492
3.93
3.93
34
31.846
33.133
34.421
3.89
3.89
35
30.916
32.151
33.386
3.84
3.84
36
30.016
31.200
32.385
3.80
3.80
37
29.144
30.281
31.418
3.75
3.75
38
28.319
29.425
30.534
3.76
3.77
39
27.486
28.532
29.579
3.67
3.67
40
26.697
27.701
28.704
3.62
3.62
45
23.116
23.931
24.745
3.40
3.40
50
20.071
20.731
21.391
3.18
3.18
55
17.474
18.008
18.542
2.96
2.96
60
15.253
15.684
16.115
2.75
2.75
65
13.351
13.697
14.043
2.53
2.53
66
13.004
13.335
13.666
2.48
2.48
67
12.668
12.984
13.301
2.44
2.44
68
12.341
12.644
12.947
2.39
2.39
69
12.024
12.313
12.603
2.35
2.35
70
11.716
11.993
12.269
2.31
2.31
71
11.418
11.682
11.946
2.26
2.26
72
11.128
11.380
11.633
2.22
2.22
73
10.846
11.088
11.329
2.18
2.18
74
10.574
10.804
11.034
2.13
2.13
75
10.308
10.528
10.748
2.09
2.09
76
10.051
10.260
10.469
2.04
2.04
77
9.800
10.000
10.200
2.00
2.00
78
9.550
9.748
9.945
2.03
2.03
79
9.306
9.503
9.699
2.07
2.07
80
9.070
9.265
9.459
2.10
2.10
81
8.841
9.033
9.226
2.13
2.13
82
8.618
8.809
9.000
2.17
2.17
83
8.402
8.591
8.780
2.20
2.20
84
8.192
8.379
8.566
2.23
2.23
85
7.987
8.172
8.358
2.27
2.27
86
7.789
7.972
8.155
2.30
2.30
87
7.596
7.778
7.959
2.33
2.33
88
7.409
7.589
7.768
2.37
2.37
89
7.227
7.405
7.583
2.40
2.40
90
7.050
7.226
7.402
2.43
2.43
91
6.878
7.052
7.226
2.47
2.47
92
6.711
6.883
7.055
2.50
2.50
93
6.548
6.889
6.718
2.53
2.53
94
6.558
6.390
6.727
2.57
2.57
95
6.237
6.403
6.569
2.60
2.60
96
6.087
6.252
6.417
2.63
2.63
97
5.942
6.105
6.268
2.67
2.67
98
5.800
5.961
6.122
2.70
2.70
99
5.663
5.822
5.981
2.73
2.73
100
5.529
5.686
5.844
2.77
2.77
105
4.912
5.060
5.208
2.93
2.93
110
4.371
4.511
4.651
3.10
3.10
3.898
115
4.030
4.161
3.27
3.27
120
3.482
3.730
3.606
3.43
3.43
Figure 630 (Thermistor Values)
Summary of Contents for VRP12K
Page 46: ...46 OPERATION Component Identification Indoor Coil 36k ...
Page 48: ...48 OPERATION Component Identification Outdoor Coil Monitored by 1 thermistor ...
Page 49: ...49 OPERATION Component Identification Outdoor Fan BLDC Variable Speed 600 1000 RPM ...
Page 53: ...53 OPERATION Component Identification 4 Way Reversing Valve 208 230v Reversing valve assembly ...
Page 177: ...177 UPDATING VRP FIRMWARE Or ...
Page 184: ...184 UPDATING VRP FIRMWARE Open zip file Copy to SD Card Insert into SD Card Slot ...
Page 193: ...193 UPDATING VRP FIRMWARE Retrieving VRP Data Remove SD Card from FMC and Locate DF Folder ...
Page 196: ...196 WIRINGDIAGRAMS 12 24K BTU 208 230V 7 5 10 0 KW Figure 801 Wiring Diagram ...
Page 197: ...197 WIRING DIAGRAMS 12 24K BTU 208 230V 2 5 3 4 5 0 KW Figure 802 Wiring Diagram ...
Page 198: ...198 WIRING DIAGRAMS 12 24K BTU 265V 2 5 3 4 5 0 kW Figure 803 Wiring Diagram ...
Page 199: ...199 WIRING DIAGRAMS 12 24K BTU 265V 7 5 10 kW Figure 804 Wiring Diagram ...
Page 200: ...200 WIRING DIAGRAMS 36K BTU 208 230V Figure 805 Wiring Diagram ...