137
PB
COMPONENTS TESTING
Mcs Motor Control System Board Pin out
12V
GND
RS485 - Y
RS485 - Z
12V
GND
RS485 - A
RS485 - B
L1
L2
Ground
Fuses
U
V
Compressor Pinout
W
1. Check power from pins 1 to 2 for 12 volts.
2. Check power from pins 5 to 6 for 12 volts.
3. Check power from Line 1 to ground for appopriate voltage.
4. Check power from Line 2 to ground for appropriate voltage.
5. Remove power from the unit and allow two minutes for capacitors to discharge before attempting to take continuity readings.
6. Check for continuity on the fuses. If fuses are blown, replace MCS board.
Figure 616 (MCS Board)
Summary of Contents for VRP12K
Page 46: ...46 OPERATION Component Identification Indoor Coil 36k ...
Page 48: ...48 OPERATION Component Identification Outdoor Coil Monitored by 1 thermistor ...
Page 49: ...49 OPERATION Component Identification Outdoor Fan BLDC Variable Speed 600 1000 RPM ...
Page 53: ...53 OPERATION Component Identification 4 Way Reversing Valve 208 230v Reversing valve assembly ...
Page 177: ...177 UPDATING VRP FIRMWARE Or ...
Page 184: ...184 UPDATING VRP FIRMWARE Open zip file Copy to SD Card Insert into SD Card Slot ...
Page 193: ...193 UPDATING VRP FIRMWARE Retrieving VRP Data Remove SD Card from FMC and Locate DF Folder ...
Page 196: ...196 WIRINGDIAGRAMS 12 24K BTU 208 230V 7 5 10 0 KW Figure 801 Wiring Diagram ...
Page 197: ...197 WIRING DIAGRAMS 12 24K BTU 208 230V 2 5 3 4 5 0 KW Figure 802 Wiring Diagram ...
Page 198: ...198 WIRING DIAGRAMS 12 24K BTU 265V 2 5 3 4 5 0 kW Figure 803 Wiring Diagram ...
Page 199: ...199 WIRING DIAGRAMS 12 24K BTU 265V 7 5 10 kW Figure 804 Wiring Diagram ...
Page 200: ...200 WIRING DIAGRAMS 36K BTU 208 230V Figure 805 Wiring Diagram ...