19
PB
SPECIFICATIONS
Supply Air Flow and Data
MODEL
VHA 09/12
VHA 18
VHA 24
FAN SPEED
LOW
HIGH
LOW
HIGH
LOW
HIGH
ESP (“)
CFM
0.0”
470
520
730
800
755
805
0.05”
460
510
670
735
700
750
0.10”
430
490
630
675
660
700
0.15”
410
470
595
640
615
665
0.20”
360
440
550
600
575
625
0.25”
310
400
505
550
525
580
0.30”
260
350
455
500
485
540
0.35”
--
--
400
445
450
500
0.40”
--
--
345
400
415
465
Condenser External Static Pressure
Model
Design
Maximum
CFM
ESP ("WC)
ESP ("WC)
VHA09
650
0.03
0.12
VHA12
650
0.03
0.12
VHA18
950
0.03
0.12
VHA24
980
0.03
0.12
Indoor air flow may be determined by measuring the external static pressure (ESP) of the duct system using an inclined
manometer or magnahelic gauge and consulting the above chart to derive actual air flow. Under no circumstances
should the large chassis Vert-I-Pak equipment be operated at an external static pressure in excess of 0.4” W.C. Operation
of the Vert-I-Pak under these conditions will result in inadequate air flow, leading to poor performance and/or
premature component failure.
Control
For LOW speed only operation, connect the fan output terminal from the thermostat to the GL terminal of the electronic
control.
For HIGH speed only operation, connect the fan output terminal from the thermostat to the GH terminal of the electronic
control.
For thermostats with two-speed capability, connect the LOW speed output to the GL terminal and the HIGH speed output
to the GH terminal.
Condenser CFM & External Static Pressure
VPAK is designed to install through an exterior wall with a plenum (VPAWP-8, VPAWP-14) and a Friedrich external louver .
NOTE: If the Friedrich designed plenum and louver combinations are not used, the selections and design must be evaluated
by Friedrich to ensure the total pressure drop does not exceed the maximum allowable limits.
Figure 210 (Indoor CFM & External Static Pressure)
Figure 211 (
Condenser CFM & External Static Pressure)
Summary of Contents for VERT-I-PAK VHA-18K75RTP
Page 62: ...62 TROUBLESHOOTING TroubleshootingChart Cooling FIGURE 719 TROUBLESHOOTING...
Page 76: ...76 PARTS CATALOG 9K 12KRefrigerationAssy 6 9 5 3 14 1 2 11 7 8 10 4 12 13 Figure 902...
Page 78: ...78 PARTS CATALOG 9K 12K208 230V 3 1 2 8 7 5 9 6 10 11 4 Figure 903...
Page 80: ...80 PARTS CATALOG 9K 12K265V 9 10 3 12 13 14 18 11 1 7 6 2 4 19 15 16 17 8 Figure 904...
Page 82: ...82 PARTS CATALOG 18KUnitAssembly 3 8 4 6 5 9 10 1 2 7 Figure 905...
Page 89: ...89 PARTS CATALOG 18KBlowerAssembly 8 1 2 3 7 5 10 9 4 6 Figure 908...
Page 91: ...91 PARTS CATALOG 24KBlowerAssembly 9 7 2 3 4 1 8 Figure 909...
Page 93: ...93 PARTS CATALOG 18K 230V ControlBox 1 4 5 3 7 8 2 6 9 Figure 910...
Page 95: ...95 PARTS CATALOG 24K 230V ControlBox 12 1 9 11 3 5 2 10 6 13 8 7 4 Figure 911...