110
PB
TROUBLESHOOTING
Diagnostic Codes
No.
Malfunction
Name
Display Method of Indoor Unit
Display Method of Outdoor Unit
A/C status
Possible Causes
Dual‑8
Code
Display
Indicator Display (During blinking,
ON 0.5s and OFF 0.5s)
Indicator has 3 kinds of display status
and during blinking, ON 0.5s and
OFF 0.5s
Power
Indicator
Cool
Indicator
Heating
Indicator
Yellow
Indicator
Red
Indicator
Green
Indicator
1
High
Pressure
Protectioon
Of System
E1
OFF 3s
and blink
once
During cooling and drying
operation, except indoor
fan operates, all loads stop
operation.
During heating operation, the
complete unit stops.
Possible reasons:
1.Refrigerant was super‑
abundant;
2.Poor heat exchange
(including filth blockage of
heat exchanger and bad
radiating environment );
Ambient temperature is
too high.
2
Antifreezing
protection
E2
OFF 3s
and blink
twice
OFF 1 s
and blink 3
times
During cooling and drying
operation, compressor and
outdoor fan stop while indoor
fan operates.
1.Poor air‑return in indoor
unit;
2.Fan speed is abnormal;
3.Evaporator is dirty.
3
In Defect of
refrigerant
F0
OFF 1 s
and blink 9
times
The Dual‑8 Code Display will
show F0 and the complete
unit stops.
1.In defect of refrigerant;
2.Indoor evaporator
temperature sensor works
abnormally;
3. The unit has been
plugged up somewhere.
4
High
Discharge
temperaature
protection of
compressor
E4
OFF 3s
and blink 4
times
OFF 1s
and blink 7
times
During cooling and drying
operation, compressor and
outdoor fan stop while indoor
fan operates. During heating
operation, all loads stop.
Please refer to the malfunc‑
tion analysis (discharge
protection, overload).
5
Overcurrent
protection
E5
OFF 3s
and blink 6
times
OFF 1s
and blink 5
times
During cooling operation,
compressor stops while
indoor fan motor operates.
During heating operation, the
complete unit stops.
1. Supply voltage is unstable;
2. Supply voltage is too low
andload is too high;
3. Evaporator is dirty.
6
Communica‑
tion malfunc‑
tion
E6
OFF 3s
and blink 6
times
Always on
During cooling operation,
compressor stops while
indoor fan motor operates.
During heating operation,
the complete unit stops.
Refer to the corresponding
malfunction analysis.
7
High
temperature
resistant
prtoection
E8
OFF 3s
and blink 8
times
OFF 1s
and blink 6
times
During cooling operation:
compressor will stop while
indoor fan will operate.
During heating operation, the
complete unit stops.
Refer to the malfunction
analysis (overload, high
temperature resistant).
8
EEPROM
malfunction
EE
OFF 3s
and blink
15 times
OFF 1s
and blink
11 times
During cooling and drying op‑
eration, compressor will stop
while indoor fan will operate;
During heating operation, the
complete unit will stop
Replace outdoor control
panel AP1
Summary of Contents for FSHW091
Page 8: ...8 INTRODUCTION FSHSW09A1A FSHSW12A1A Figure 102 Indoor Units FSHSW18A3A FSHSW24A3A FSHSW36A3A ...
Page 47: ...47 INSTALLATION ...
Page 48: ...48 INSTALLATION Installation Tools ...
Page 72: ...72 WIRED CONTROLLER Display ...
Page 122: ...122 TROUBLESHOOTING Malfunction of IDUFanMotorU8 Service Manual No Start End ...
Page 146: ...146 WIRING DIAGRAMS Figure 8054 9 12KOutdoorUnitWiringDiagrams 60000706067401 3 2 N 1 C3 C4 ...
Page 158: ...158 FIgure 906 PARTS CATALOG 9KOutdoorUnit 28 27 29 31 30 32 ...
Page 160: ...160 PARTS CATALOG 12k OutdoorUnit 28 27 29 31 30 32 FIgure 907 ...