2 Safety instructions
2
8
Rittal Liquid Cooling Package
4. Origin of reused refrigerant
5. Amendments to and replacement of system com-
ponents
6. Results of all regular routine checks and
7. Any significant shutdowns.
2.3.3
F-gas regulation
Regulation (EC) No. 517/2014 of the European Parlia-
ment and of the Council of 16 April 2014 on certain fluor-
inated greenhouse gases entered into force on 9 June
2014. The Regulation regulates the reduction of emis-
sions, the use, recovery and destruction of certain fluor-
inated greenhouse gases, and the labelling and disposal
of products and equipment containing such gases.
Leak test pursuant to Article 4 (leak checks)
The leak checks shall be carried out with the following
frequency, depending on the CO2 equivalent quantities
of fluorinated greenhouse gases.
–
5 t – 50 t
at 12-month intervals, (or where a leakage
detection system is installed, at least every
24 months),
–
50 t – 500 t
at 6-month intervals, (or where a leakage
detection system is installed, at least every
12 months),
–
more than 500 t
at 3-month intervals, (or where a
leakage detection system is installed, at least every
6 months).
2.3.4
Chemicals – Climate Protection Ordinance
This Ordinance applies in addition to the aforementioned
Regulation (EC) No. 517/2014 of the European Parlia-
ment and of the Council of 16 April 2014.
2.4
RoHS compliance
The LCP DX fulfils the requirements of EU Directive
2011/65/EC on the Restriction of Use of Certain Hazard-
ous Substances in Electrical and Electronic Equipment
(RoHS) of 1 July 2011.
Note:
Corresponding information about the RoHS
Directive may be found on our website at
www.rittal.com/RoHS.