Frico SIRe Basic Quick Manual Download Page 1

SIRe Basic 

Quick guide

SIReB

C

Original instructions

.

... 42

IT  

.

... 70

RU  

.

... 14

GB  

.

... 35

FR  

.

... 63

PL  

.

... 7

SE  

.

...49

NL  

.

... 21

DE  

.

... 56

NO 

.

...28

ES 

.

... 77

FI 

Summary of Contents for SIRe Basic

Page 1: ...SIRe Basic Quick guide SIReB C Original instructions 42 IT 70 RU 14 GB 35 FR 63 PL 7 SE 49 NL 21 DE 56 NO 28 ES 77 FI...

Page 2: ...L N L PE L 230V C2 X5 C1 X4 ROOM X3 Pot Unit ID ACTUATOR SUPPLY N L N L PE L 230V C2 X5 C1 X4 ROOM X3 Pot Unit ID ACTUATOR SUPPLY N L N L PE L 230V SIReCC6XX max 50 m SIReB1 B2 B1EC SIReB1 B2 B1EC SIR...

Page 3: ...SUPPLY N L N L PE L 230V C2 X5 C1 X4 ROOM X3 Pot Unit ID ACTUATOR SUPPLY N L N L PE L 230V C2 X5 C1 X4 ROOM X3 Pot Unit ID ACTUATOR SUPPLY N L N L PE L 230V SIReCC6XX max 50 m SIReCC6XX max 50 m SIRe...

Page 4: ...4 1 SE GB Wiring diagram Advanced SIRe B1 B2 B1EC 2...

Page 5: ...5 OK OK 4 3a Wiring diagram Advanced 8 7 0 1 2 3 4 5 6 9 3b 1 0 OK...

Page 6: ...6 5 www frico se...

Page 7: ...able accessories e g actuator see wiring diagram When several units are connected set a unique ID for each unit 1 9 which is set in the ID selector of the SIReB1 B2 B1EC Each unit should have a unique...

Page 8: ...SIRe Basic Activate heat 0 No heat 1 Heat step 1 possible 2 Heat step 2 possible 3 Heat step 3 possible Heat steps controlled by thermostat Start up Set desired room temperature 5 30 C Set fan steps...

Page 9: ...odular cable RJ12 6 6 5 SIReCC610 Modular cable RJ12 6 6 10 SIReCC615 Modular cable RJ12 6 6 15 SIReCC640 Modular cable RJ12 6 6 40 SIReCC403 Modular cable RJ11 4 4 3 SIReCC405 Modular cable RJ11 4 4...

Page 10: ...AC VKF VLSP Type Description Connection VLSP15LF Pressure independent DN15 VLSP15NF Pressure independent DN15 VLSP20 Pressure independent DN20 VLSP25 Pressure independent DN25 VLSP32 Pressure independ...

Page 11: ...l mode Decrease the temperature setting below 5 C and the following symbols are shown in the status window manual mode In manual mode both fan and heating steps are controlled manually Fan over run Wh...

Page 12: ...his does not affect the unit s safety P 02 Over run time Time when the fan continue to run when the heat has been on P 03Temperature limit for over run Over run time is cancelled if the internal tempe...

Page 13: ...tact Frico PC board SIReB1 B2 B1EC ID 0 Interrupt the power supply and select different ID numbers for all SIReB1 B2 B1EC in the system Two or more SIReB1 B2 B1EC have the same ID number Interrupt the...

Page 14: ......

Page 15: ......

Page 16: ......

Page 17: ...ce Frico AB Tel 46 31 336 86 00 Box 102 SE 433 22 Partille mailbox frico se Sweden www frico se For latest updated information and information about your local contact www frico se Art no 201854 2017...

Reviews: