
210.100-IOM (JUL 2018)
Page 15
ACUAIR
®
HYGIENIC AIR UNITS
INSTALLATION
INSULATION OF THE BASE RECONNECT SEAM
OF AN ACUAIR PERFORMANCE SERIES UNIT
When two AcuAir unit sections are drawn together the base
channels of the two sections form an uninsulated cavity that
under certain conditions could produce condensation. AcuAir
provides a ship loose foam insulation kit to fill this cavity as
part of the reconnect procedure.
On the Performance Series air units this insulation must be
injected from underneath the unit after the sections have
been securely joined.
Follow the instructions in the section "FOAM KIT 15 USE
GUIDELINES" on page 21 for preparing the two part foam
mixture and the injection kit. Take special note of the 30
second inactivity limit after which the injection nozzle may
become permanently clogged.
Foam should be injected into the cavity at a rate of 3 - 4
bd-ft per linear foot of seam. This will mean a 15 bd-ft can
of expanding foam will fill between 4 - 5 linear ft of AcuAir
reconnect seam.
INTERNAL RECONNECT
(AcuAir Performance Series Only)
.25 MINIMUM DIA. PARALLEL CONTINUOUS BEADS OF
POLYURETHANE CAULKING REQ’D (BOTH FACES OF SPLIT)
PRIOR TO REASSEMBLING
RECONNECT, HOUSING, AND
HARDWARE NOT SHOWN THIS SIDE
FOR CLARITY
HOUSING
Foam Injected
From Underneath
Figure 12 – Foam Injection Underneath Base Assembly Attachment - Relates to AcuAir Performance Series Unit Only
NOTICE
INJECT THE FOAM INTO THE OPEN SEAM AFTER THE
AIR UNIT SECTIONS HAVE BEEN SECURELY
RECONNECTED.
NOTICE
IF FOAM DISPENSING HAS STOPPED FOR MORE THAN
30 SECONDS, REPLACE THE NOZZLE WITH THE
EXTRA PROVIDED.
Summary of Contents for AcuAir
Page 54: ......