Wire Replacement I/O (900 MHz): User Manual and Reference Guide
Transmit Rate
Setting
Description
(1) Normal
Terminal Menu:
(3) Edit Transmission Characteristics > (3) Xmit Rate
Description:
The setting for normal operation of the radio is
1
.
l
When set to
0
, the radios transmit back and forth continuously regardless
if they have any actual data.
l
0
should only be used as a diagnostic tool and not for normal operation.
l
The strength of the signal may be gauged by the Clear to Send (CTS)
LED.
l
A solid red CTS LED indicates a strong signal.
l
A blinking CTS LED indicates a weaker signal.
4.2 Setting Other MultiPoint Parameters
Set these parameters in the
MultiPoint Parameters
tab.
These settings are available in the MultiPoint Parameters menu in the terminal interface and apply
to both standalone or integrated wire replacement I/O systems and to I/O Master and I/O Slave
models unless indicated otherwise in their description.
4.2.1 1 PPS Enable Delay
1 PPS Enable Delay
Setting
Description
Default Setting:
255
Options:
255 to disable 1 PPS
0 to 254 to enter the delay
Terminal Menu:
(5) Edit MultiPoint Parameters > (9) 1 PPS Enable/Delay
Description:
The 1 PPS Enable/Delay setting allows a 1 PPS signal to propagate from the
I/O Master to all I/O Slaves in a MultiPoint network. When this parameter is
enabled a properly generated pulse applied on the DTR line of the I/O Master
provides a 1 PPS pulse on the CD line of any I/O Slave in the network.
Follow the steps below to use the 1 PPS Enable/Delay feature.
Setup 1PPS Enable/Delay
1. Set the
1 PPS Enable/Delay
parameter to
0
in the Master.
Note
: The I/O Master must have a 1 PPS pulse on the DTR pin.
LUM0008AG Rev Sep-2015