Operation Test
The manual mode of operation is used to perform the operation test and can be used to prime the foam pump
if it is required.
The water pump is not operated during this procedure.
If a monitored function is not within normal parameters the
FLOW
display shows an error or fault warning
code and a description shows in the message display. (Refer to Error Codes or Fault Warning Codes .)
TFC100 Operation Note:
The TFC100 does not have a message display. Information is only shown in the
4-digit display, procedures are the same. (Substitute
MODE
for
MENU
button.)
Set-up
Do the Pre-Operation Checks.
Fill the tank (water can be used for this test).
Open the foam tank shutoff valve.
Set manual selector valve to the foam tank with fluid. Close flush valves.
Place a calibrated collection bucket under the calibration bypass valve hose.
Set the calibration bypass valve to bypass.
Supply power to the system,
OFF
is shown in the
FLOW
display.
Ensure no error or fault warning codes show in the display.
Test
1. Press the
ON/OFF
and
PRESET
buttons at the same time and hold.
Results:
MANUAL MODE
flashes in the message display for 3 seconds, the message display changes to
show
USE +/– FOR FLOW
, the
FLOW
display flashes. (TFC100 flashes the
ON/OFF
LED, the
FLOW
LED is on.)
TFC400 only:
Press the
A/B
button to select the tank with fluid.
2. Press the
+
and
–
buttons to set the flow rate.
Results: The
FLOW
display shows the operator entered flow rate, the message display shows moving
arrows to indicate the foam concentrate pump RPM, and the foam pump pumps fluid into the bucket.
3. Pump until a steady stream flows.
Do not operate the pump dry for more then 30 seconds. If no fluid flows shut down the pump check
for air leaks, closed valve, reversed check valve, clogged strainer screen etc. in all lines between
the tank and foam pump input.
4. Press the
ON/OFF
button to shut down the TurboFoam system, the LED goes off. Press the
ON/OFF
button again, the LEDs comes on, the system powers on in the manual mode.
5. To exit the manual mode, cut power to the control module.
6. Set the calibration bypass valve control back to the operate position.
Follow-up Calibrations
The flow sensor and concentrate pump must be calibrated before normal system operations. Refer to
Calibration, Maintenance, and Troubleshooting; Calibration Section and perform the Calibrate Discharge Flow
Sensor and Calibrate Foam Concentrate Pump procedures.
If the TankVision Pro is installed, ensure program codes P314 and P315 are set and the TankVision Pro is calibrated.
Summary of Contents for Turbofoam TFC100
Page 69: ...TFC100 Rev180215 69 CONTROL MODULES Figure P1 TurboFoam Control Modules 6 7 5 4 3 2 1 ...
Page 81: ...TFC100 Rev180215 81 MANUAL ABF SELECTOR Figure P7 Manual ABF Selector 9 8 6 5 4 3 2 1 7 ...
Page 85: ...TFC100 Rev180215 85 NOTES ...
Page 86: ...TFC100 Rev180215 86 NOTES ...
Page 87: ...TFC100 Rev180215 87 NOTES ...
Page 88: ...TFC100 Rev180215 88 ...