The TurboFoam system automatically injects foam concentrate into the water flow to provide a consistent
foam solution at the discharge regardless of water flow fluctuations.
When power is supplied to the system, the control module
FLOW
display shows
OFF
, the message display
shows the date and time or total flow rate for all sensors when a summing box is installed.
When the
ON/OFF
button is pressed the LED comes on and the control module is active in the auto mode.
The
FLOW
display shows the water discharge flow rate
The % display shows the last used value or the preset value (based on program code P116).
The message display shows
AUTO A(B)
and moving arrows to indicate the foam concentrate pump RPM.
With a TankVision Pro connected and program set for tank status (codes P314,P315) the message display
shows the foam type and time remaining at current flow rates
A XX.Xm
.
Note:
The program allows the end user to set the range and the specific increments that are used to
control foam percentage concentration with the
+
and
–
buttons.
The
PRESET
or the
+
and
–
buttons are used to adjust the amount of concentrate (changing the percent)
injected into the discharge water flow to create the foam solution. Both of these functions are programmable to
meet the operators requirements.
If a monitored function is not within normal parameters the
FLOW
display shows an error or fault warning code
and a description shows in the message display. (Refer to Table 5. Error Codes or Table 6. Fault Warning Codes.)
The remote on/off switch and indicator option duplicate the
ON/OFF
button and LED. The optional flush
on/off switch and indicator controls the optional flush valve.
Detailed Information
TFC100
The TFC100 does not have a message display. Information is shown in a 4-digit display and on four LEDs.
Operations are the same as TFC200/300/400, substitute
MODE button
for
MENU
button in procedure steps.
The TFC100 control module four LEDs indicate the display mode for the 4-digit display;
%FOAM, TOTAL
FOAM, FLOW,
and
TOTAL WATER
. Press and release the
MODE
button to toggle through the display modes.
Foam and water totals are reset to 0 when power goes off. When
TOTAL FOAM
or
TOTAL WATER
is shown
on the display,
press and hold the
MODE
button to reset total to 0.
TFC200/300/400
The
MENU
button allows the operator to gain access to detailed information and some programming features.
Press the
MENU
button to scroll detailed information and return to normal display.
The total water or total foam values can be reset to zero (0) when shown in the display by holding the
MENU
button until the number 0 flashes in the display.
The message display reverts to normal operation after ten (10) seconds if no button is pressed.
Message Display
Description
T WATER
* Shows total amount of water flow (in gallons or liters)
T FOAM
* Shows total amount of foam concentrate flow (in gallons or liters)
WATER FLOW
Shows water flow rate for each discharge;
active only with summing box installed
, use the
+
and
–
buttons to scroll
TANK A
Shows foam concentrate left in tank A;
active only with TankVision Pro Foam A installed
TANK B
Shows foam concentrate left in tank B;
active only with TankVision Pro Foam B installed
FAULT CODES
Shows stored faults with date and time; use the
+
and
–
buttons to scroll
INCIDENT REPORT
Shows stored incidents with date and time; use the
+
and
–
buttons to scroll
Table 4. Detailed Information
*Note:
The total water and total foam flow amounts are reset to zero when the system is powered
down. These can be reset during operations if required.
Summary of Contents for Turbofoam TFC100
Page 69: ...TFC100 Rev180215 69 CONTROL MODULES Figure P1 TurboFoam Control Modules 6 7 5 4 3 2 1 ...
Page 81: ...TFC100 Rev180215 81 MANUAL ABF SELECTOR Figure P7 Manual ABF Selector 9 8 6 5 4 3 2 1 7 ...
Page 85: ...TFC100 Rev180215 85 NOTES ...
Page 86: ...TFC100 Rev180215 86 NOTES ...
Page 87: ...TFC100 Rev180215 87 NOTES ...
Page 88: ...TFC100 Rev180215 88 ...