![FRC TCA200 Manual Download Page 22](http://html1.mh-extra.com/html/frc/tca200/tca200_manual_2329241022.webp)
TCA200 Rev171031
22
CALIBRATION
The following program functions are available to view and change once the
calibration password code has been entered:
C1 - Discharge Pressure Sensor Zero Calibration
C2 - Intake Pressure Sensor Zero Calibration
Refer to Calibration Programs.
Calibration Programs
The calibration password code is set from the factory as 1111.
Enter Calibration Password Code
Note:
To exit the programming mode press the
SILENCE
button when the
program code is flashing in the
RPM
display.
1. Press the
SILENCE
button and hold it until the
RPM
display shows four
dashes
– – – –
and the message display shows
enter----
. Release the
button.
2. Press the
MENU
button within three seconds. The
RPM
display shows the
number 1000. Each time the
MENU
button is pressed the first digit scrolls
up by 1. Set the first digit to the number desired.
3. Press the
SILENCE
button to move the curser to the next digit. Press the
MENU
button to change the digit.
4. Repeat step 3 and enter the password code 1111.
Result: When a correct code is entered
C 1
flashes in the
RPM
display.
The program revision
D.Sensor Set P=0?
scrolls in the message display.