12VDC Transducer
(FCS Provided)
Pump Quickstart Guide
Wiring
Verify correct input voltage
and wiring to the VFD power
and motor terminals. Connect
3-phase input power wires
to VFD terminals R, S & T or
single-phase power wires to
VFD terminals R & S.
Connect 3-phase motor wires to
VFD terminals U, V & W.
Connect power source ground
wire and motor ground wire to
VFD ground terminal.
DRV
T/K 0.0A
00 STP 0.00Hz
Mode:
Use to cycle through parameter groups:
SET>DRV>FG1>FG2>....
Up & Down:
Use to cycle through parameters
of the current group. Use to adjust parameters
when in programming mode.
Loc/Rem:
Toggles between Local and Remote
operation
Enter:
Use to enter programming mode of
any parameter as well to submit a change.
A flashing cursor will appear when VFD is in
programming mode.
Shift:
Use to cycle backwards through
parameter groups. When in programming
mode, use to shift cursor to the right (one
position per press).
Rev, Stop/Reset & Fwd:
Use to Start and Stop
VFD Forward or Reverse in Local mode. Use
Stop to reset VFD fault.
1
2
3
4
5
6
Keypad Programming
1
2
3
4
5
6
VFD Only
Enclosed VFD
Verify correct input voltage and
wiring to enclosed VFD panel
power and motor terminals.
Connect 3-phase input power
wires to enclosure or disconnect
terminals L1, L2 & L3 or single-
phase power wires to terminals
L1 & L2.
Connect 3-phase motor wires to
enclosure terminals T1, T2 & T3.
Connect power source ground
wire and motor ground wire to
enclosure ground terminal.
Warning: Input, Output and Control wiring must be in separate conduits
Note:
Do not
wire any wire to the DC bus
“P1”, “P2”
& “
N
” terminals.
L1 L2 L3
L1 L2 L3
L1 L2
L1 L2
Transducer verification
– From main DRV-00 screen
go to DRV-98 by pressing Down key . The reading is in
4-20mA range and it should match to transducer output
current. If reading is less than 4mA, verify transducer wir-
ing and voltage on V+ and 24 terminals.
Enclosed Drive Instructions:
(terminals mounted on back panel)
Stand Alone Drive Instructions:
Transducer placement:
Placing the transducer too
close to the pump discharge may cause oscillations and
improper operation of the VFD.
Note: If two transducers are used for redundancy, refer to
VFD manual for details.
Main Display:
DRV -
Current parameter group. (SET, DRV, FG1, FG2, I/O, APP, EXT & COM)
00L -
Shows the current parameter number within a current group. An ‘L’ will appear when VFD is switched
to Local control mode by either LOC/REM key or digital input.
T -
Shows source for VFD start/stop operation (
T
= Remote,
K
= Keypad,
O
= Communication Protocol).
K -
Shows source for VFD frequency command (
K=
Keypad,
V=
0-10VDC,
I=
4-20mA,
O=
Communication)
0.0A -
Shows the actual motor current
STP -
Shows the current status of the VFD (
STP
= Stop,
FWD
= Forward,
REV
= Reverse)
0.00Hz -
Shows
frequency reference or PID set-point in VFD stop mode and actual VFD output frequency
in VFD run mode.
R S T G P1 P2 N U V W
R S T G P1 P2 N U V W
L1 L2 L3
L1 L2 L3
T1 T2 T3
T1 T2 T3
M
M
M
M
3-PHASE POWER
3-PHASE POWER
SINGLE-PHASE POWER
ENCLOSED VFD
ENCLOSED VFD
SINGLE-PHASE POWER
MOTOR
MOTOR
MOTOR
MOTOR
VFD
Terminals
L
VFD
Terminals
Transducer:
franklin-controls.com | 800.962.3787
Terminal Blocks
12 VDC Transducer
(FCS Provided)
AG
V
1
(BLACK)
(SILVER)(shield)
(RED)
Terminal Blocks
V
+
1. Peel back insulation to expose shield (bare) wire.
Note: Green & White wires should not be used.
2. Wire the pressure transducer's positive RED wire to the
terminal marked V+ for 12VDC and the output BLACK
wire to terminal with the shield wired to AG.
Instructions
12 VDC Transducer
(FCS Provided)
AG
V
1
(BLACK)
(SILVER)(shield)
(RED)
Terminal Blocks
V
+
12 VDC Transducer
(FCS Provided)
AG
V
1
(BLACK)
(SHIELD)(bare wire)
(RED)
Terminal Blocks
V
+
*Note: Use “5G” for 7.5-40HP VFDs and “CM” for
VFDs over 40HP
12VDC Transducer (FCS Provided)
*(CM) 5G
V+
I
(BLACK)
(SHIELD)
(bare wire)
(RED)
Notes:
1) Put shrink tube or electrical tape on
bare shield wire to prevent short circuit of
any VFD terminals.
2) Wiring may vary for non-FCS provided
transducers
5G
24
I
*(CM)
*Note: For VFD’s 40HP and smaller, wire the
transducer shield to CM and place a wire
jumper between CM & 5G.’
24VDC Transducer
(POWER)
(SHIELD)
(bare wire)
(SIGNAL)
WARNING: Submersible pumps can develop very high pressure in some situations. Always use
a properly selected and installed pressure relief valve to prevent damage and injury from over-
pressurization of pipes and tanks. Installation of cut-off pressure switch is recommended.
Control Wiring:
The start dry contact should be wired to VFD terminals CM and M7 or 1 and 2 in
enclosed VFD panel. If jumper is installed on start terminals, VFD will run when power turned on.