REPLACEMENT 

PART 

INSTRUCTIONS 

Memory Backup Battery Replacement Instructions  

for Tank Sentinel, AutoStik, & BulkStik  ATGs 

Parts & Materials 
Required:

   

One 

new

 3 volt lithium 

battery (INCON P/N: 
TSSP-BAT / 390-0004), a 
thin piece of adhesive tape, 
and a digital multimeter with 
test probes. 

Diagram:  

 

Testing the  
Battery ( B1 )

 

Use a digital multimeter set 
to read 5 DC volts and 
measure the DC voltage 
between the  

+

 battery 

terminal and  

– 

ground or 

the yellow-colored metal 
shield  
(+2.8 to +3.3 volts DC is good).   

 

When to Test the  

Battery Voltage (Schedule)

:  Yearly after the first two years of operation or use.

 

 

DANGER   Electrical Shock Hazard. 

 Make sure all safety shields are installed to 

prevent electrical shocks — 

DO NOT

 touch any device other than the battery. 

 

Removal & Installation Steps

  

( with Tank Gauge Power  ON  &  SW 1  ON ):

 

1.) 

Printout the complete system and tank setup reports

 for all tanks.  ( 

Note

 – if the 

power goes out or is turned off while the battery is out of its holder then all of the 
setup/programmed values of the system will be lost.  If this happens then the entire 
tank gauge will have to be reprogrammed ). 

WEDGE UP HERE

ABOUT 1/8 INCH

Battery Cutaway

Side View

b

PRY OUT HERE

a

Yellow 

colored 

metal 

shield

b

TS-1001/N-N   U10

 VER No.     DATE

a

 

Replace the battery if the voltage reading is below 

2.8 volts DC 