![Franklin Electric SUBMONITOR CONNECT MT1111 Installation And Operation Manual Download Page 56](http://html1.mh-extra.com/html/franklin-electric/submonitor-connect-mt1111/submonitor-connect-mt1111_installation-and-operation-manual_2328834056.webp)
SPECIFICATIONS
SMS3R Ratings
56
SMS3R Ratings
SMS Ratings - Non-Combination. NEMA 3R
Model:
SMS3R-
UL HP / MAX AMPS / SCIC
Protection
Range
SubMonitor
Connect
Overload
Model
3-Phase
200 VAC
208 VAC
230 VAC
460 VAC
575 VAC
HP
A
kA HP
A
kA HP
A
kA HP
A
kA HP
A
kA
S00/M
2
7.8
5
2
7.8
5
3
9.6
5
5
7.6
5
7.5
9
5
1A-DPV
MT2211
S0P/M
7.5
25.3
5
7.5
24.2
5
10
28
5
15
21
5
20
22
5
1A-DPV*
MT2211
S1P/M
15
48.3
5
15
46.2
5
15
42
5
30
40
5
30
32
5
1A-DPV*
MT2211
S2/M
20
62.1
5
20
59.4
5
25
68
5
40
52
5
50
52
5
1A-DPV*
MT2211
S3/M
30
92
10
30
88
10
40
104
10
60
77
10
75
77
10 1A-DPV*
MT2211
S3P/M
30
92
10
30
88
10
40
104
10
75
96
10
75
77
10 1A-DPV*
MT2211
S4/M
40
120
10
40
114
10
50
130
10
100
124
10
100
99
10 1A-DPV*
MT1311
S4P/M
60
177
10
60
169
10
75
192
10
150
180
10
-
-
-
1A-DPV*
MT1311
S5/M
100
285
18
100
273
18
125
312
18
250
302
18
-
-
-
1A-DPV*
MT1311
S5P/M
125
359
18
125
343
18
150
360
18
300
361
18
-
-
-
1A-DPV*
MT1311
*DPV = Differs per Motor Voltage
SMS Ratings - Combination. NEMA 3R
Model:
SMS3R-
UL HP / MAX AMPS / SCIC
Protection
Range
SubMonitor
Connect
Overload
Model
3-Phase
200 VAC
208 VAC
230 VAC
460 VAC
575 VAC
HP
A
kA HP
A
kA HP
A
kA HP
A
kA HP
A
kA
S0/M-G15
2
8
50
2
8
50
2
8
50
5
8
25
5
8
14 6A-8A
MT2211
S0/M-G20
3
11
50
3
11
50
3
11
50
7.5
11
25
10
11
14 8A-11A
MT2211
S0P/M-G30
3
17
50
5
17
50
5
17
50
10
17
25
15
17
14 12A-17A
MT2211
S1/M-G40
5
22
50
5
22
50
7.5
22
50
15
22
25
20
22
14 16A-22A
MT2211
S1P/M-G50
7.5
28
50
7.5
28
50
10
28
50
20
28
25
25
28
14 20A-28A
MT2211
S1P/M-G60
10
34
50
10
34
50
10
34
50
25
34
25
30
32
14 24A-DPV*
MT2211
S2/M-G80
10
45
50
10
45
50
15
45
50
30
45
25
40
45
14 32A-45A
MT2211
S2/M-G100
15
57
50
15
57
50
20
57
50
40
52
25
50
52
14 40A-DPV*
MT2211
S3/M-G100
15
57
50
15
57
50
20
57
50
40
57
25
50
57
14 40A-57A
MT2211
S3/M-G125
20
71
65
20
71
65
25
71
65
50
71
35
60
71
18 50A-71A
MT2211
S3P/M-G150
25
85
65
25
85
65
30
85
65
60
85
35
75
77
18 60A-DPV*
MT2211
S4/M-G200
30
114
65
40
114
65
40
114
65
75
114
35
100
99
18 80A-DPV*
MT1311
S4/M-G250
40
120
65
40
114
65
50
130
65
100
124
35
-
-
-
100A-DPV*
MT1311
S5/M-G300
50
171
65
60
171
65
60
171
65
125
171
35
-
-
-
120A-171A
MT1311
S5/M-G400
75
228
65
75
228
65
75
228
65
150
228
35
-
-
-
160A-228A
MT1311
S5P/M-G500
100
285
65
100
285
65
100
285
65
200
285
35
-
-
-
200A-285A
MT1311
S5P/M-G600
100
342
65
100
342
65
125
342
65
250
342
35
-
-
-
240A-342A
MT1311
S5P/M-G800
125
359
65
125
343
65
150
360
65
300
361
35
-
-
-
320A-DPV*
MT1311
*DPV = Differs per Motor Voltage
575V SMS Ratings - Non-Combination. NEMA 3R
Model:
SMS3R-
UL HP / MAX AMPS / SCIC
Protection
Range
SubMonitor
Connect
Overload
Model
3-Phase
200 VAC
208 VAC
230 VAC
460 VAC
575 VAC
HP
A
kA HP
A
kA HP
A
kA HP
A
kA HP
A
kA
S4P/6M
-
-
-
-
-
-
-
-
-
-
-
-
150
144
10 1A-144A
MT1311
S5/6M
-
-
-
-
-
-
-
-
-
-
-
-
250
242
18 1A-242A
MT1311
S5P/6M
-
-
-
-
-
-
-
-
-
-
-
-
300
289
18 1A-289A
MT1311
Summary of Contents for SUBMONITOR CONNECT MT1111
Page 1: ...franklinwater com SUBMONITORCONNECT Installation and Operation Manual ...
Page 73: ...ESPAÑOL ES franklinagua com SUBMONITORCONNECT Manual de instalación y funcionamiento ...
Page 153: ...franklinwater com FRANÇAIS FR SUBMONITORCONNECT Manuel d installation et d utilisation ...
Page 229: ...NOTES 77 NOTES ...
Page 230: ...NOTES 78 NOTES ...