PRODUCT INFORMATION
Pump Sizing and Performance
9
Pump Sizing and Performance
Maximum pump output using the SubDrive Utility is similar to the performance achieved using a
pressure switch. Therefore, the pump selection criteria are the same as if a pressure switch were
used.
Refer to the Franklin Electric AIM Manual for specific sizing information.
If a pump and motor as described above are already installed in the system, and the well system
components are in good working order, no further system upgrades are required. However, if the
existing pump and motor have not been properly chosen, or if the components of the well system
are not in good working order, the SubDrive Utility cannot be used to correct the problem or
extend the life of aging components.
Generator Sizing
Basic generator sizing for the Franklin Electric SubDrive Utility is 1.5 times the maximum input
watts consumed by the drive, rounded up to the next normal-sized generator.
Recommended minimum generator size for the SubDrive Utility is 6000 watts nominal.
IMPORTANT:
Do not use with a Ground Fault Circuit Interrupter (GFCI). If using an externally regu-
lated generator, verify that the voltage and hertz are appropriate to supply the drive. Not compati-
ble with inverter-controlled generators.