DRIVE PROGRAMMING
Default Settings Table - ADV Menu
54
Default Settings Table - ADV Menu
Parameters in highlighted rows are reset when the application is changed
[SET–00]
.
Default Settings Table - PROT Menu
CODE
Display
Basic
Supply Fan
Exhaust
Fan
Cooling
Tower
Centrifugal
Pump
Submersible
Pump
Vacuum
Pump
Constant
Torque
PM Motor
MagForce
ADV-00 Upper Bound Int
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
ADV-01 PID Out Limit
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
ADV-02 Password Input
0
0
0
0
0
0
0
0
0
0
ADV-03 Parameter Reset
Disable
Disable
Disable
Disable
Disable
Disable
Disable
Disable
Disable
Disable
ADV-05 Password Lock
Unlocked
Unlocked
Unlocked
Unlocked
Unlocked
Unlocked
Unlocked
Unlocked
Unlocked
Unlocked
ADV-06 Acc/Dec Type
Linear
Linear
Linear
Linear
Linear
Linear
Linear
Linear
Linear
Linear
ADV-07 Acc/Dec Format Unit 0.1 sec Unit 0.1 sec Unit 0.1 sec Unit 0.1 sec Unit 0.1 sec Unit 0.1 sec Unit 0.1 sec Unit 0.1 sec Unit 0.1 sec Unit 0.1 sec
ADV-08 Energy Saving
Disable
Disable
Disable
Disable
Disable
Disable
Disable
Disable
Disable
Disable
ADV-09 EnergySave Gain
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
ADV-10 MMC Mode
Disable
Disable
Disable
Disable
Disable
Disable
Disable
Disable
Disable
Disable
ADV-11
Motor Quantity
1
1
1
1
1
1
1
1
1
1
ADV-12
Aux Mtr Stop Hz
0
0
0
0
0
0
0
0
0
0
ADV-13
Alt Run Time
720 min
720 min
720 min
720 min
720 min
720 min
720 min
720 min
720 min
720 min
ADV-14 S-Start ON Dly
1 sec
1 sec
1 sec
1 sec
1 sec
1 sec
1 sec
1 sec
1 sec
1 sec
ADV-15
S-Start Off Dly
1 Sec
1 Sec
1 Sec
1 Sec
1 Sec
1 Sec
1 Sec
1 Sec
1 Sec
1 Sec
ADV-16 Mtr Switch Tmr
10 Sec
10 Sec
10 Sec
10 Sec
10 Sec
10 Sec
10 Sec
10 Sec
10 Sec
10 Sec
ADV-17
Mtr Switch Hz
60 Hz
60 Hz
60 Hz
60 Hz
60 Hz
60 Hz
60 Hz
60 Hz
115 Mz
115 Hz
ADV-18 Lag Start Freq
59.5 Hz
59.5 Hz
59.5 Hz
59.5 Hz
59.5 Hz
59.5 Hz
59.5 Hz
59.5 Hz
114 Hz
114 Hz
ADV-19 Lag Start Delay
10 Sec
10 Sec
10 Sec
10 Sec
10 Sec
10 Sec
10 Sec
10 Sec
10 Sec
10 Sec
ADV-20 Lag Start Level
2%
2%
2%
2%
2%
2%
2%
2%
2%
2%
ADV-21
Lead Freq Drop
10 Hz
10 Hz
10 Hz
10 Hz
10 Hz
10 Hz
10 Hz
10 Hz
10 Hz
10 Hz
ADV-22 MMC Dec Time
2 Sec
2 Sec
2 Sec
2 Sec
2 Sec
2 Sec
2 Sec
2 Sec
2 Sec
2 Sec
ADV-23 Lag Stop Freq
35 Hz
35 Hz
35 Hz
35 Hz
35 Hz
35 Hz
35 Hz
35 Hz
50 Hz
70 Hz
ADV-24 Lag Stop Delay
4 Sec
4 Sec
4 Sec
4 Sec
4 Sec
4 Sec
4 Sec
4 Sec
4 Sec
4 Sec
ADV-25 Lag Stop Level
0.3%
0.3%
0.3%
0.3%
0.3%
0.3%
0.3%
0.3%
0.3%
0.3%
ADV-26 Lead Freq Bump
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
ADV-27 MMC Accel Time
2 Sec
2 Sec
2 Sec
2 Sec
2 Sec
2 Sec
2 Sec
2 Sec
2 Sec
2 Sec
ADV-28 Power on Delay T
10 Sec
10 Sec
10 Sec
10 Sec
10 Sec
10 Sec
10 Sec
10 Sec
10 Sec
10 Sec
ADV-29 Run Delay Timer
0 Sec
0 Sec
0 Sec
0 Sec
0 Sec
0 Sec
0 Sec
0 Sec
0 Sec
0 Sec
ADV-30 Backspin Timer
0 Sec
0 Sec
0 Sec
0 Sec
0 Sec
0 Sec
0 Sec
0 Sec
0 Sec
0 Sec
ADV-34 Min Run Timer
0 Sec
0 Sec
0 Sec
0 Sec
0 Sec
0 Sec
0 Sec
0 Sec
0 Sec
0 Sec
ADV-55 AVR Select
Enable
Enable
Enable
Enable
Enable
Enable
Enable
Enable
Enable
Enable
CODE
Display
Basic
Supply Fan
Exhaust
Fan
Cooling
Tower
Centrifugal
Pump
Submersible
Pump
Vacuum
Pump
Constant
Torque
PM Motor
MagForce
PROT-00 Decel Method
Normal
Normal
Normal
Normal
Normal
Normal
Normal
Normal
Normal
Normal
PROT-01 Preheat Level
0%
0%
0%
0%
0%
0%
0%
0%
0%
0%
PROT-02 Preheat Duty
0%
0%
0%
0%
0%
0%
0%
0%
0%
0%
PROT-03 LV Level
By VFD
rating
By VFD
rating
By VFD
rating
By VFD
rating
By VFD
rating
By VFD
rating
By VFD
rating
By VFD
rating
By VFD
rating
By VFD
rating
PROT-04 OV Stall level
By VFD
rating
By VFD
rating
By VFD
rating
By VFD
rating
By VFD
rating
By VFD
rating
By VFD
rating
By VFD
rating
By VFD
rating
By VFD
rating
PROT-05 OV Stall Prevent
Standard
Standard
Standard
Standard
Standard
Standard
Standard
Standard
Standard
Standard
PROT-06 SW Brake V Lvl
By VFD
model
By VFD
model
By VFD
model
By VFD
model
By VFD
model
By VFD
model
By VFD
model
By VFD
model
By VFD
model
By VFD
model
PROT-07 OCA Level
120%
120%
120%
120%
120%
120%
120%
120%
120%
120%
PROT-08 OCN Level
120%
120%
120%
120%
120%
120%
120%
120%
120%
120%
PROT-10 Auto Restarts
3
3
3
3
3
3
3
3
3
3
PROT-11 AutoRetry Delay
120 Sec
120 Sec
120 Sec
120 Sec
120 Sec
120 Sec
120 Sec
120 Sec
120 Sec
120 Sec
PROT-12 OL-2 Type
Disable
Disable
Disable
Disable
Disable
Disable
Disable
Disable
Disable
Disable
PROT-13 OL-2 Level
120%
120%
120%
120%
120%
120%
120%
120%
120%
120%
PROT-14 OL-2 Delay
0.1 Sec
0.1 Sec
0.1 Sec
0.1 Sec
0.1 Sec
0.1 Sec
0.1 Sec
0.1 Sec
0.1 Sec
0.1 Sec
Summary of Contents for Cerus X-Drive
Page 2: ......
Page 3: ...CERUS X DRIVE INSTALLATION AND OPERATION MANUAL Firmware Version 1 1 Franklin Electric Co Inc ...
Page 94: ...COMMUNICATIONS BACnet Communication 94 ...
Page 98: ...ACCESSORIES Optional Extension Cards 98 Frame D Frame E Frame F ...
Page 99: ...ACCESSORIES Optional Extension Cards 99 Frame G Frame H ...