SPECIFICATIONS
460V Class 1~75HP (5.5~55kW)
237
460V Class 1~75HP (5.5~55kW)
(1)
UL Type 1 kit comes with UL Open Type VFD which are Frame D and larger.
(2)
The VFD cannot produce output voltage greater than input voltage.
(3)
Variable torque (VT) motor rating based on a 120% overload for 1 minute. Constant Torque (CT) motor rating based
on 120% overload for 1 minute and 160% overload for 3 seconds.
Model (CXD-xxx-4V)
UL Type 1
(1)
003A 004A 005A 008A 010A 013A 018A 024A 032A 038A 045A 060A 073A 091A 110A
Frame Size
A
B
C
D0
Input Ratings
Voltage
380 (- 15%) ~ 480 VAC (+ 10%)
Frequency
50/60 Hz (± 5%)
Current -
Variable Torque
4.3
6
8.1
12.4
16
20
22
26
35
42
50
66
80
91
110
Current -
Constant Torque
3.5
4.3
5.9
8.7
14
15.5
17
20
26
35
40
47
63
74
101
Output Ratings
Carrier Freq
2.0 - 15.0kHz
2.0 - 10.0kHz
Voltage
(2)
3-phase, 380 ~ 480 VAC
(3)
Frequency
0.01 ~ 599 Hz
Efficiency
98%
Power Factor
>0.98
Weight kg (lbs.)
2.6 ± 0.3 (5.8 ± 0.7)
5.4 ± 1 (11.9 ± 2.2)
9.8 ± 1.5 (21.6 ± 3.3)
27 ± 1 (59.5 ± 2.2)
DC Choke
None
Built-in 3%
VFD Ratings with 3-Phase Input Power
Variable
Torque
Motor
(3)
Ratings
Max Amps
3
4.2
5.5
8.5
10.5
13
18
24
32
38
45
60
73
91
110
Capacity [kVA]
2.4
3.3
4.4
6.8
8.4
10.4
14.3
19
25
30
36
48
58
73
88
Max HP @ 460 V
Surface Motor
1.5
2
3
5
5
7.5
10
15
20
25
30
40
50
60
75
Max HP @ 460 V
4” Submersible
1
2
3
5
5
5
10
10
15
–
–
–
–
–
–
Max HP @ 460 V
6” Submersible
–
–
–
–
5
7.5
10
15
20
20
25
30
40
50
60
Max HP @ 460 V
8” Submersible
–
–
–
–
–
–
–
–
–
–
–
40
50
60
75
Constant
Torque
Motor
(3)
Ratings
Max Amps
1.7
3
4
6
9
10.5
12
18
24
32
38
45
60
73
91
Capacity [kVA]
2.2
2.4
3.2
4.8
7.2
8.4
10.4
14.3
19
25
30
36
48
58
73
Max HP @ 460 V
.75
1.5
2
3
5
5
7.5
10
15
20
25
30
40
50
60
VFD Ratings with 1-Phase Input Power
Variable
Torque
Motor
Ratings
Max Amps
1.5
2.1
2.75
4.25
5.25
6.5
9
12
16
19
22.5
30
36.5
30
36.3
Max HP @ 460 V
Surface Motor
.5
1
1
2
3
3
5
7.5
10
10
15
20
25
20
25
Max HP @ 460 V
4” Submersible
.5
.5
1
2
2
3
5
5
7.5
10
10
15
–
–
–
Max HP @ 460 V
6” Submersible
–
–
–
–
–
–
5
5
7.5
10
10
15
20
15
20
Max HP @ 460 V
8” Submersible
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
Constant
Torque
Motor
Ratings
Max Amps
0.8
1.5
2
3
4.5
5.3
6
9
12
16
19
22.5
30
24.1
30
Max HP @ 460 V
0.25
.5
.75
1.5
2
3
3
5
7.5
10
10
15
20
20
20
Summary of Contents for CERUS X-DRIVE CXD-003A-4V
Page 2: ......
Page 3: ...CERUS X DRIVE INSTALLATION AND OPERATION MANUAL Firmware Version 1 2 Franklin Electric Co Inc ...
Page 96: ...OPERATION Protection Features 96 ...
Page 112: ...ADVANCED APPLICATION OPTIONS Multi Drive Configurations 112 ...
Page 124: ...COMMUNICATIONS BACnet Communication 124 ...
Page 128: ...ACCESSORIES Optional Extension Cards 128 Frame D Frame E Frame F ...
Page 129: ...ACCESSORIES Optional Extension Cards 129 Frame G Frame H ...
Page 132: ...ACCESSORIES Optional Extension Cards 132 ...
Page 234: ...PARAMETER REFERENCE TABLES Parameter Descriptions Motor Menu 234 ...
Page 250: ...GLOSSARY 250 ...