PARAMETER REFERENCE TABLES
Parameter Descriptions > ADVANCE Menu
215
Parameter Descriptions > ADVANCE Menu
AR = Adjustable while running.
IO-74
0586 N D-Inputs State
0000h - FFFFh
Digital Inputs State: Displays status of digital inputs numbered in hex for
-
mat. The input status is in binary format. Empty box indicates that N.O. DI is
deactivated and solid box that it is activated. It shows DIs FWD, REV, DI1,
DI2… status from the right to the left Bit0=1, Bit1=2, Bit3=4, Bit4=8, Bit5=16,
etc. Example below shows hex value=5 and solid boxes (activated) for Bit0
(value=1) DI (FWD) and Bit2 (value=4) DI (DI1). The contacts wired to those
inputs should be closed to deactivate input and open to activate it.
IO-75
0587 N D-Relays Status 0000h - FFFFh
Displays status of digital outputs (DOs) numbered in hex format. The output
status is in binary format. Empty box indicates that output Relay is deacti
-
vated and solid box that it is activated. It shows DOs RA1, RA2…status from
the right to the left Bit0, Bit1, Bit2, Bit3, etc. Example below shows hex
value=1 and solid box (activated) for Bit0 (RA1). The N.O. contact of RA1
relay is closed until selected function is activated.
IO-76
0588 Y AI Loss Freq
Freq Low Limit to Freq High
Limit
When
[IO-01]
or
[IO-06]
is set to
4_At AI Loss Freq
and signal loss is detected,
VFD will run at
[IO-76]
frequency.
CODE Mod
Bus AR Display Name
Range
Description
CODE Mod
Bus AR Display Name
Range
Description
ADV-00 0768 Y Upper Bound Int 0 to 100%
Upper limit for the integral gain (I), which limits the output frequency.
Upper Limit Freq =
VFD Max Freq Main [VFD-00]
x
Upper Bound Int [ADV-00]
.
Too large integral value will cause a slow response at sudden load changes,
and this could cause motor stall or machine damage.
ADV-01 0769 Y PID Out Limit
0 to 110%
Maximum PID command limit. Percentage of Maximum Output Frequency
[VFD-00]
.
ADV-02 0770 Y Password Input
0 to 65535
Password protect from modifying parameters.
ADV-03 0771 N Parameter Reset 0_No Function
1_Write protect
2_--------
3_Reset KWH
4_Reset all Param
5_Reset M Run Time
Select stored data to be reset or enable Write protection.
ADV-05 0773 Y Password Lock
0_Unlocked
1_Locked
When setting password protection for the first time, set password in
Pass
-
word Input [ADV-02]
and then
Password Lock [ADV-05]
becomes
1_Locked
. To per
-
manently disable password protection, unlock parameters by entering
password in
Password Input [ADV-02]
and then set
Password Lock [ADV-05]
to
0_Unlocked
. If drive is unlocked by a password and password lock is not set to
0_Unlocked
, the next reboot of the VFD will lock the VFD again.
Summary of Contents for CERUS X-DRIVE CXD-003A-4V
Page 2: ......
Page 3: ...CERUS X DRIVE INSTALLATION AND OPERATION MANUAL Firmware Version 1 2 Franklin Electric Co Inc ...
Page 96: ...OPERATION Protection Features 96 ...
Page 112: ...ADVANCED APPLICATION OPTIONS Multi Drive Configurations 112 ...
Page 124: ...COMMUNICATIONS BACnet Communication 124 ...
Page 128: ...ACCESSORIES Optional Extension Cards 128 Frame D Frame E Frame F ...
Page 129: ...ACCESSORIES Optional Extension Cards 129 Frame G Frame H ...
Page 132: ...ACCESSORIES Optional Extension Cards 132 ...
Page 234: ...PARAMETER REFERENCE TABLES Parameter Descriptions Motor Menu 234 ...
Page 250: ...GLOSSARY 250 ...